FPC1000 Biometric Controller User Manual

V1.00

 

Page 43 of 43 

 

Chapter 5 FAQ

 

NO 

Descriptions 

Possible Reason 

Solution 

 

No lights, not responding 

 

Lights  are  ON,  card  swipe 

not responsive 

 

Power problem 

 

Card technology not 

compatible 

 

Check power supply 

 

replace card 

 

Lock stays opened 

 

Wrong lock wiring (NC/NO) 

 

Lock time too long 

 

REX Input configured wrong 

 

Exit Button short circuit 

 

Verify wiring 

 

Verify lock time 

 

Verify REX Config (NO/NC) 

 

Check Exit Button 

 

FP 

or 

card 

information 

missing 

 

Missing user information 

 

Verify enrollment 

 

Verify network connection 

 

Can  not  open  door  by 

flashing card or FP. 

 

Lock power problem 

 

Enrolment problem 

 

Access level not enabled 

 

check lock power and wiring 

 

Check enrolment 

 

Verify access level 

 

Can not open the door when 

it’s Card+FP mode     

 

Either card or fingerprint are 

not enrolled 

 

Card  and  fingerprint  not 

enrolled with same user 

 

 

Door bell not working 

 

wiring error 

 

 

Wrong Time/Date   

 

Setting was not complete 

 

No PC sync 

 

Set Time/Date in manage menu. 

 

FPC1000 does not respond 

with Fingerprint 

1. 

finger positioned wrong

 

2. 

Pressure applied with 
finger

 

3. 

Unit overheating 

 

1. 

lay  finger  flat  covering  the 

glass

 

2. 

Do not apply pressure

 

3. 

Cool  unit  down.  Do  not  install 

in direct sunlight.

 

 

Содержание BioUSB10P

Страница 1: ...User Manual Thank you for purchasing Keyking products Please read before installing FPC 1000 Fingerprint stand alone networked door controller...

Страница 2: ...14 3 4 TCP IP Network 15 Chapter 4 On Device Configuration Menu 16 4 2 Personnel Management 18 4 2 1 Add Personnel Administrator 18 4 2 2 Delete Personnel 23 4 2 3 Delete All 23 4 2 4 Modify 24 4 3 N...

Страница 3: ...3 of 43 3 5 Door Open Mode 40 Chapter 5 Operation in Sphinx 41 5 1 Install driver for BioUSB10 41 5 2 Select FPC1000 Series 41 5 3 Search Config FPC1000 41 5 4 Enrolling finger for user 41 5 5 Transf...

Страница 4: ...Networked Door Controller Same installation as Stand Alone with the addition of network connection to the SPHINX This allow more advanced access control functionalities as well as sharing fingerprint...

Страница 5: ...AWID Follow card up to 58BIT EM 2308 W26 W34 HID 1326 1386 According to card configuration W26 27 34 35 37 and so on KK KK243 250T W34 W50 P Multi Technology 125KHz Awid EM HID Prox Keyking and more...

Страница 6: ...KEYKING GROUP FPC1000 Biometric Controller User Manual V1 00 Page 6 of 43 1 3 FPC Family...

Страница 7: ...on as reader to standard access control controllers Wiegand 26 34 input for secondary reader as exit device Can be card reader or another FPC1000 unit Exit Button REX and Door Sensor inputs 3A Door Re...

Страница 8: ...ns instruction 1 5 1 FPC1000 works as a reader Note Do Not connect FPC to door controller as reader connect only Wiegand wires to the controller Power the FPC from independent power supply 12Vdc 1A Do...

Страница 9: ...iometric Controller User Manual V1 00 Page 9 of 43 1 5 2 FPC1000 works as a standalone 3 options Standalone no external reader Notes recommended power supply PSRFS1240 incorporate isolation relay and...

Страница 10: ...r outdoor FPC1000 1 5 3 FPC1000 Location When selecting the location of installation make sure the following rules are followed No direct sun avoid over heating Protect from water splashes on the scre...

Страница 11: ...Ensure that the wires can go freely and connect to the unit It is recommended to cut openings the same as on the back plate to allow the connectors and the wires to be stress free 2 1 4 Mount the back...

Страница 12: ...EN Lock Open Keypad NO Key Description 0 9 0 9 Numerical Keys for menu selection and data entry 2 Esc Back to previous menu cancel operation 3 Door Bell energize Relay 2 4 Delete data entered 5 Scroll...

Страница 13: ...tches IN1 AUX Input wire J2 NO1 Door Lock Relay See corresponding lock type for wiring COM1 NC1 NO2 AUX Programmable Relay Also act as Alarm and Alarm Clock COM2 NC2 J3 D1_Out Wiegand Output Signal D0...

Страница 14: ...relay and backup battery support REX Exit Button o May be connected via the PSRFS1240 in such case do not use Door Sensor to prevent false alarms from the unit o Or direct to the FPC1000 using GND SEN...

Страница 15: ...ING GROUP FPC1000 Biometric Controller User Manual V1 00 Page 15 of 43 3 4 TCP IP Network FPC1000 TCP IP network Figure 3 8 TCP IP crystal head Figure 3 9 Figure 3 2 RJ45 NO Definition 1 TX 2 TX 3 RX...

Страница 16: ...e Configuration Menu Below is the full configuration menu New units do not have Administrator and will allow entering the menu without password or 1234 After first Administrator is enrolled to enter t...

Страница 17: ...oll Users and Administrators When enrolling note the instructions on the screen 4 1 5 To make changes to other features and functions see the menu tree on page 15 4 1 6 More options and features are a...

Страница 18: ...Info 6 7 4 2 Personnel Management 4 2 1 Add Personnel Administrator 1 Press Menu to enter management menu when FPC1000 is idle Esc works as cancel while Enter works as confirm 2 Press 1 to enter User...

Страница 19: ...provide higher security but might result in multiple attempts by authorized users Lower number will make the unit faster to response and comply with problematic fingers but might authorize unauthorize...

Страница 20: ...ext screen Level 1 1 apply to Card Fingerprint mode ONLY The number represent how strict the verification is done 4 is normal higher number will provide higher security but might result in multiple at...

Страница 21: ...se and comply with problematic fingers but might authorize unauthorized persons False Positive FP Card mode prevent false positive Hit ENTER to go to the next screen 4 Follow the instructions on the s...

Страница 22: ...2 1 5 User ID card 1 Press 5 to enter add UserID Card This mode uses Dual Factor ID though do not use Fingerprint as one of the identifications It is not recommended to use this mode unless there is...

Страница 23: ...erminal Info 2 3 Keyking FPC1000 1 Add 2 Delete 3 Modify 4 Add Admin 5 Delete All Keyking FPC1000 Delete all Y 1 N 2 4 2 2 Delete Personnel 1 Enter the main menu and select 1 User 3 Press 2 Delete 4 E...

Страница 24: ...OD 123456 Keyking FPC1000 1 User 2 Network 3 Option 4 Device 5 Terminal Info 2 3 Keyking FPC1000 1 Add 2 Delete 3 Modify 4 Add Admin 5 Delete All Keyking FPC1000 Input UserID MOD 123456 4 2 4 Modify 1...

Страница 25: ...or updates from time to time make sure the laptop has static ip also so the FPC1000 will automatically recognize it when connected Single laptop can be used to configure multiple FPC1000 units See SPH...

Страница 26: ...SC key to go back to previous Network Configuration menu Keyking FPC1000 1 Terminal ID 2 Net Configure 3 IP Address 4 Subnet Mask 5 Gateway 6 Host IP 7 Host Port Keyking FPC1000 1 User 2 Network 3 Opt...

Страница 27: ...3 Enter IP Address interface button is Delete Backspace button is and ENTER to confirm Use ESC to go back to previous Network Configuration menu Keyking FPC1000 IP Address 192 168 x x Keyking FPC1000...

Страница 28: ...Mask 3 Enter Subnet Mask button is Delete Backspace button is and ENTER to confirm Use ESC to go back to previous Network Configuration menu Keyking FPC1000 Subnet Mask 255 255 x x Keyking FPC1000 1 T...

Страница 29: ...t Mask 3 Enter Gateway button is Delete Backspace button is and ENTER to confirm Use ESC to go back to previous Network Configuration menu Keyking FPC1000 1 User 2 Network 3 Option 4 Device 5 Terminal...

Страница 30: ...Network 3 Select 4 to enter Subnet Mask 4 Enter Gateway button is Delete Backspace button is and ENTER to confirm Use ESC to go back to previous Network Configuration menu Keyking FPC1000 1 Terminal I...

Страница 31: ...2 Network 2 Select 7 Host Port 3 Enter Port number button is Delete Backspace button is and ENTER to confirm Use ESC to go back to previous Network Configuration menu Keyking FPC1000 1 Terminal ID 2...

Страница 32: ...creen Saver 4 Door Relay 5 MultiFP Verify 6 Tamper Alarm Keyking FPC1000 Clock Setting 20170103130923 4 4 Option 4 4 1 Language 1 In Main Menu select 3 Option 2 Select 1 Language 3 Select language 0 E...

Страница 33: ...dark if no key or finger had been pressed It is important to select the right time to allow reasonable time to read the screen for users and at the same time to conserve energy by turning off the scre...

Страница 34: ...Too long others unauthorized may be able to enter following authorized entrance tailgating Door Status is the Door Sense input Usually a magnet relay such as used in alarm systems It is not mandatory...

Страница 35: ...cuts paper cut cracked skin on their enrolled finger having two or more fingers enrolled will allow entrance in such cases Multiple Fingerprint enrollment is possible only using SPHINX software for en...

Страница 36: ...the whole unit Some can be personalized during the enrollment process to match personal conditions It is recommended to NOT make any changes unless needed to 1 From the Main Menu select 4 Device 2 Se...

Страница 37: ...etting Use this setting if connecting the FTP1000 as Fingerprint Reader to a Door Controller using Wiegand Protocol This type of connection provides higher security operation where the door is control...

Страница 38: ...No UserID 6 CardNo UserName 7 CardNo Name UserID 4 5 3 Card Number Mode Card Number Mode set the display of the card number on the screen Display Mode 4 7 It does not affect the operation of the FPC10...

Страница 39: ...PC1000 1 User 2 Network 3 Option 4 Device 5 Terminal Info 6 7 Keyking FPC1000 Device ID 0001 Version 1 00 Language English MAC 00 10 F0 00 43 1D IP 192 168 4 207 8 4 5 5 Terminal Initialize 1 From Dev...

Страница 40: ...emains closed Note Only the registered personnel can pass verifying 2 FP Card Application Flash a registered card or FP FPC1000can control a door by FP Card 3 FP Card Application Flash a registered ca...

Страница 41: ...go to Setup menu and select communication configuration 2 Select the fingerprint tab 3 Select FPC1000 Series 5 3 Search Config FPC1000 1 run the Controller Configuration process as any other controlle...

Страница 42: ...43 5 5 Transfer to FPC1000 terminal 5 6 FPC1000 setting Here you can change the Company name and everything When you click Apply then done Company Name Default Welcome to Use Tamper Alarm Display Mode...

Страница 43: ...rmation Verify enrollment Verify network connection 4 Can not open door by flashing card or FP Lock power problem Enrolment problem Access level not enabled check lock power and wiring Check enrolment...

Отзывы: