OPERATION MANUAL

RK-2001W2

SOLID FUEL FIRED

BOILER TEMPERATURE CONTROLLER

Version C112

Содержание RK-2001W2

Страница 1: ...OPERATION MANUAL RK 2001W2 SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Version C112 ...

Страница 2: ......

Страница 3: ... be placed in a measurement hole in the boiler Pictures 2 and 3 shows diagram of electrical connection of the controller CAUTION Before plugging in the controller check if the wiring system is properly grounded and if the terminal screws of the output connector are properly screwed CAUTION Total power of the fan central heating pump and hot water pump which are connected to the controller musn t e...

Страница 4: ... 50ºc hold up of burning in WORK mode 50ºU heating of hot water in SUMMER mode 70ºd total bacteria control heating up of hot water up to 75ºC 4 Setting up the user parameters Holding OK button enters the user mode and allows to review and is indicated by fast flashing of the room thermostat indicator You can look through the parameters with and arrow buttons After choosing the desired parameter yo...

Страница 5: ...utton E g 70 d will appear on the display After reaching 75 C in the hot water tank the controller will return to its state before choosing this option CAUTION the total bacteria control function can switched on at night when the water from the hot water tank is not used to prevent the users from burn injury 4 4 Water temperature readout in hot water tank 50 this parameter shows the measured tempe...

Страница 6: ...ater 1 hot water priority 2 no hot water priority 3 mixing pump 0 3 1 0 L 45 Minimum boiler temperature 30 65 1ºC 45 H 85 Maximum boiler temperature 80 90 1ºC 85 h 2 Boiler temperature hysteresis 1 10 1ºC 2 A 99 Boiler overheating temperature 90 99 1ºC 99 Fd2h Fuel shortage testing time with burning 1 99 4h 1min 2h Fb2h Fuel shortage testing time in WORK mode and burning out 1 99 4h 1min 2h Ar 0 W...

Страница 7: ...rameter When this parameter is set to a value between 0 and 10 it defines time in minutes of gradual increase of fan speed from its minimum value n 40 to value r 50 for smooth start Fan work time Πn15 time of turning the fan on for a while to remove accumulated gases Setting the parameter to turns this function off This function can be active in WORK mode Fan pause time Nu 6 time between fan work ...

Страница 8: ...water pump working with priority ur 2 value hot water tank working without priority ur 3 value means controlling of the returning water mixing pump in the boiler with the launch temperature of u 50 and hysteresis uh 5 5 4 Boiler work temperature setting Minimum boiler temperature L 45 minimum temperature which you can set with the boiler thermostat knob Maximum boiler temperature H 85 maximum temp...

Страница 9: ...arm by pressing STOP button 5 7 Additional output Additional output work mode Ar 0 the controller is equipped with a multipurpose output that can work in one of following modes Ar 0 mode output may control oil or gas boiler if such boiler exists in the heating circuit After switching the controller on with the main power switch the additional boiler is turned off and it turnes on again when there ...

Страница 10: ...e mode when no buttons are pressed for 1 minute 6 Additional functions To improve comfort in heated rooms the controller has been equipped with an input allowing to connect any kind of room thermostat with contact output When temperature in the room is below desired temperature the central heating pump is turned on and the room thermostat indicator is lit It means that the boiler should keep tempe...

Страница 11: ... is necessary proceed as follows turn the master switch off disconnect the power of the boiler remove the controller from the slot in the boiler disconnect all connectors with leads from the controller 9 Specifications Voltage 230V 10 50Hz Power consumption 4VA Temperature measurement range 9 109 C 1 C Boiler temperature adjustment range 30 90 C 1 C Programmed boiler overheating protection 90 99 C...

Страница 12: ...12 Picture 2 RK 2001W2 connection diagram Picture 3 UM 1 module connection diagram ...

Страница 13: ...0 Tap hot water desired temperature uh 5 Hot water heating hysteresis ur 0 Work mode of hot water pump 0 no hot water 1 hot water priority 2 no hot water priority 3 mixing pump L 45 Minimum boiler temperature H 85 Maximum boiler temperature h 2 Boiler temperature hysteresis A 99 Boiler overheating temperature Fd2h Fuel shortage testing time with burning Fb2h Fuel shortage testing time in WORK mode...

Страница 14: ...14 ...

Страница 15: ......

Страница 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohaterów Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl ...