25
Note:
▲
When the protective device is a residual current device(RCD), Ia is the rated
residual operating current I
Δ
n.
For instance in a TN system with a nominal mains voltage of Uo =
230
V
protected by type gG fuses the Ia and maximum Zs values could be:
Rating
Disconnecting Time
5
s
Disconnecting Time
0
.
4
s
(A)
Ia (A)
Zs (
Ω
)
Ia (A)
Zs (
Ω
)
6
28
8
.
20
47
4
.
90
10
46
5
.
00
82
2
.
80
16
65
3
.
60
110
2
.
10
20
85
2
.
70
147
1
.
56
25
110
2
.
10
183
1
.
25
32
150
1
.
53
275
0
.
83
40
190
1
.
21
320
0
.
72
50
250
0
.
92
470
0
.
49
63
320
0
.
71
550
0
.
42
80
425
0
.
54
840
0
.
27
100
580
0
.
39
1020
0
.
22
If the prospective fault current is measured, its value must be higher than the
Ia value of the protective device concerned.