24
When the protective device is a residual device (RCD), Ia is the rated residual
operating current I
Δ
n. For example in a TT system protected by an RCD the
maximum RA values are as follows:
Rated residual
operating
current I
Δ
n mA
10
30
100
300
500
1000
Ra (at
50
V)
Ω
5000
1667
500
167
100
50
Ra (at
25
V)
Ω
2500
833
250
83
50
25
For this example the maximum value is
1667
Ω
, the loop tester reads
12
.
74
Ω
and consequently the condition RA ≤
50
/Ia is met. It is also important
to test the operation of the RCD using the RCD function in accordance with
BS
7671
.
The following condition shall be fulfilled for each circuit.
Zs ≤ Uo/Ia where Zs is the earth fault loop impedance voltage is the nominal
voltage between phase and earth and Ia is the current that causes the
automatic disconnection of the protective device within the time stated in the
following table.
Uo (Volts)
T (seconds)
120
0
.
8
230
0
.
4
400
0
.
2
>
400
0
.
1
Fig.
21
LOOP/PSC/PFC