11
Display
Dot Matrix LCD
160
(W) X
240
(H) pixels.
Overload protection
The continuity test circuit is protected by a
0
.
5
A/
600
V fast acting (HRC) ceramic fuse
mounted in the battery compartment, where a
spare fuse is also stored.
The insulation resistance test circuit is
protected by a resistor against
1000
V AC for
10
seconds.
5
.
4
Applied standards
Instrument operating
IEC/EN
61557
-
1
,
2
,
3
,
4
,
6
,
10
(
1997
)
Standard
Safety standard
IEC/EN
61010
-
1
(
2001
),
CATIII (
300
V) -Instrument
IEC/EN
61010
-
031
(
2001
),
CATII (
250
V)-Test Lead KAMP
12
CATIII (
600
V)-Test Lead ACC
064
CATIII (
1000
V)-Test Lead ACC
064
SP
Protection degree
IEC
60529
(
1989
+ A
1
) IP
40
EMC
EN
61326
・
EN
55022
・
EN
61000
-
4
-
2
(performance criterion C)
・
EN
61000
-
4
-
3
(performance criterion B)
This manual and product may use the following symbols adopted from
International Safety Standards;
CAT.III
Designed to protect against transient overvoltages in a building
wiring installation (low-voltage distribution level)
Equipment protected throughout by DOUBLE INSULATION
or REINFORCED INSULATION;
Caution (refer to accompanying documents)
Caution, risk of electric shock
Protection against wrong connection is up to
500
V
Earth Ground
Specification