KT4000 Temperature Controller

Operating Manual

1. Overview

KT4000 is easy-to-use and reliable dual relay output

temperature controller. It can be used as automatic

temperature control system for various electric appliances.

2. Mail Features

Acrylic panel, plastic-steel socket shell

Control heater and cooler to adjust temperature.

One setpoint and one differential .Very easy to set .

Alarm when temp exceed temperature limit or sensor error

Autosave the program setting when power down.

2. Specifications

Power Supply: 110Vac±15% , 50/60hz

Temperature control range:-19.9~199.9

Return difference :1.0~30

Temperature control accuracy: ±1

Screen resolution : 0.1

Temperature sensor : NTC Waterproof sensor 2m/6.56ft

Output Relay Contact Capacity: 16A, 100-240Vac

3. Product picture

Left heating socket

connect with heater.

Right cooling socket

connect with refrigerator/cooler.

Dimensions:

Control panel: 92x50x17mm (3.6x1.97x0.67inch)

Socket: 208x66x40mm (8.2x2.6x1.57inch)

4. Key Instruction

: Cool output indicator. When this light on, cooling

socket have power output. Cooler start to work ; When the

light flash, cooling socket output delay .

:

Heat output indicator. When this light on, heating

socket have power output. Heater start to work.

:

Temperature alarm.When the temperature exceed the

limit range of AL~AH, this light flash and buzzer alarm.

Operation

In normal working status, the screen display

RT

(real time

temperature detected from sensor). press once. it display

temperature set value LS(see code table). press once. it

display differential value Ld.

The screen backlight will closed after 10minutes

no-operation.

In normal working status, press

SET

for 3s to enter setting

parameter mode. The screen display LS. Press

or

to

increase or decrease LS value. Then press

SET

to go into

next code Ld. Press or to adjust value.

Using the same way to set code value from LS~CA one by

one (see code table). After finishing all setting, press

SET

for 3seconds to save the setting and return to normal

display. If no key operation after finishing all settings

within 30seconds, the system won’t save modified

parameter and back to normal display.

Restore factory default setting:

In normal working status, press

and

together for 3s.

The screen will display FF and restore all code to default

factory setting.

Code Table:

Basic setting

For example,we use this thermostat to control temperature

of a reptile incubator. Heating socket connect with

light.Cooling socket connect with fan.

Only need to set LS=80

. No need to change other

parameters.

Fan works when temperature

84

. Fan stop working

when temperature <80

.

Light works

w

hen temperature<76

. Light stop

working When temperature

80

.

Advanced Setting.

Set the required temperature

LS

. Then set

Ld PL AH AL

CA

. (

AH

>

LS

+

Ld , AL<LS

-

Ld).

The controller will work

in following status:

Code

Function

Set Range

Default

LS

Temperature Set Value

-19.9~199.9

68

Ld

Differential Value

1.0~30

4

PL

Set cooling delay output

0~10minutes

0

AH

Alarm high limit

-19.9~199.9

199.9

AL

Alarm low limit

-19.9~199.9

-19.9

CA

Temperature Calibration

-19.9~19.9

0