FIGURE 1.  24V MODEL PEAK CURRENT REQUIREMENTS

REMOTE ON-OFF.  

Remote on-off (X and Y models

only) is via ±RC assigned to pins of the RA 19-(X)B I/O
connector: off = no voltage, short circuit, or 0 to 0.8V, on =
4.5 to 12.5V (or 12.5 to 24.5V via 1.5K Ohms). To reverse
on-off polarity contact Kepco. There is no isolation
between ±RC, d-c output and alarm circuit. Refer to the
applicable RA 19-(X)B Manual for details.

CURRENT MONITOR. 

Current monitor (C and Y

models only) is via ±IMON assigned to pins of the RA 19-
(X)B I/O connector. Monitored Output Current (Amps) =
Voltage drop across R

EQ

 (mVolts) / R

EQ

 (mOhms) where

R

EQ

 is the sum of R

S

 (see Table 2) + trace resistance to

point where current monitor is connected, approximately
4mOhms. The voltage drop across R

EQ

 is measured

across ± IMON pins (requires millivoltmeter, range 0 to
250mV). Accuracy is ±10%; contact Kepco if greater
accuracy is required. There is no isolation between
±IMON, alarm circuit and d-c output. Refer to the applica-
ble RA 19-(X)B Manual for details.

ALARM CIRCUIT.  

Any condition which causes the

unit to be out of specified voltage/current ranges (includ-
ing overvoltage, overcurrent, overtemperature, open
sense line, ac input line failure, etc.) results in an alarm.
All models include an isolated internal relay offering nor-
mally closed and normally open contacts referenced to an
isolated common. These contacts are rated for 1A at 30V
d-c and 0.5A at 125V a-c. These contacts may be used to
configure “close on failure” or “open on failure” alarm cir-
cuits (see Figure 3 for typical alarm circuits). Refer to the
applicable RA 19-(X)B Manual for details about the follow-
ing: 1) normally open (close on failure) contacts are not
available if ±RC is used on X and Y suffix models, 2)
alarm signals are not isolated on C, X and Y models and
3) alarm configurations for multiple power supplies. 

KEYING. 

Keying of the power supply is established at

the factory. The output voltage determines which keyway
is open. When the corresponding rack adapter key (pin) is
installed by the user, only a power supply of the correct
voltage can be inserted in the rack adapter slot.

FIGURE 2.  HSF-PFC 50 WATT POWER SUPPLIES (8) INSTALLED IN RA 19-8B RACK ADAPTER

3043527

I

1

I

2

T

t

D=(t/T)

The standard 24V Model (no options) can supply Peak
current listed in Table 1 if the four conditions listed below
are met. These models include thermal protection, volt-
age shutdown type. Restart by removing a-c input; after
sufficient cooling, reapply a-c input (wait at least 30 sec-
onds).

1. Time: t 



10 Seconds

2. 

I

1

 



Peak Current (Amperes)

3. Effective Current:

 

 

 Rated current (Amperes)

4. Effective Power P 

 Maximum Power (Watts)

    (output RMS current x output voltage)

DI1

2

I

D

I2

2

+

Содержание HSF 12-4.3PFC

Страница 1: ...d models and Section IV on page 6 suffix C T X and Y OPTIONS Options are identified by suffix T PFCT offers improved efficiency less weight and the addition of a 28V 50W model C PFCC offers current mo...

Страница 2: ...line ac input line failure etc results in an alarm All models include an isolated internal relay offering nor mally closed and normally open contacts referenced to an isolated common These contacts a...

Страница 3: ...each other and each unit must be operating at between 10 to 100 of rated output current If current to the load goes below 10 for each unit in cur rent share mode all MASTER ON lights may go on see loa...

Страница 4: ...typ 200 Va c 100 load Power Factor 0 99 typ 100V a c 0 95 typ 200V a c Switching Frequency 140KHz typical TABLE 1 OUTPUT RATINGS AND SPECIFICATIONS HSF PFC 50W SERIES STANDARD NO SUFFIX MODEL HSF 3 3...

Страница 5: ...c for one minute cutout current 20 mA INSULATION RESISTANCE Between input and ground output and ground input and output 100 Megohms min 500V d c LEAKAGE CURRENT 0 24 mA maximum IEC 950 and UL 1950 120...

Страница 6: ...1 PFCC PFCT PFCX PFCY HSF 12 4 3 1 PFCC PFCT PFCX PFCY HSF 15 3 5 1 PFCC PFCT PFCX PFCY HSF 24 2 2 1 PFCC PFCT PFCX PFCY HSF 28 1 8 1 PFCC PFCT PFCX PFCY HSF 48 1 1 1 PFCC PFCT PFCX PFCY OUTPUT VOLTS...

Страница 7: ...Between input and case ground 2KV a c for one minute Between output and case ground 500V a c for one minute cutout current 20 mA INSULATION RESISTANCE Between input and ground output and ground input...

Страница 8: ...fault FIGURE 5 COMPONENT LOCATIONS When output voltage is available the green VDC ON LED is on While monitoring output voltage at the front panel test points the Output Voltage Adjust trimmer allows...

Страница 9: ...ANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com 081721 228 1532 REV 16 9 FIGURE 6 HSF PFC 50W INCLUDING SUFFIX C T X AND Y POWER SUPP...

Отзывы: