GENERAL
This section explains how to operate the ABC Power Supply. The power supply can be oper-
ated either in Local mode using the front panel keypad and LCD, or in Remote mode using
SCPI commands via the GPIB or RS 232 bus. Operation in remote mode can be simplified by
the use of the VISA driver available for download at http://www.kepcopower.com/drivers.htm.
Local mode operation includes a description of the interaction between the LCD and the front
panel keypad. Each key of the front panel is described, with a reference to a paragraph detailing
the use of that key.
3.2
REMOTE ON/OFF
Regardless of whether the unit is in local or remote mode, the output can be set to off (0V, 0A)
from a remote location by applying a logic 0 to pin 2 (0V0ASET signal) of the External Trigger
port (see to Table 2-2).
3.3
LOCAL MODE OPERATION
Local operation of the ABC Power Supply is accomplished via the 24 key keypad on the front
panel. All indications are provided by the 2-line LCD.
3.3.1
FRONT PANEL KEYPAD AND LCD
(SEE FIGURE 2-1)
The front panel keypad is comprised of 24 key, 13 dedicated to command functions, 5 dedicated
to data functions, and 6 keys that have both command and data functions When the power sup-
ply is in command entry status the command functions are effective; when the power supply is
in data entry status the data functions are effective.
3.3.1.1
COMMAND ENTRY STATUS
Indicated by blinking colon (:) on bottom line of LCD; the power supply is waiting for a command
to be entered; data will not be accepted (accompanied by brief audible buzz). The LCD indi-
cates the actual voltage and current at the output terminals. When the output is disabled (LCD
bottom line reads Output OFF), the power supply is in Command entry status even though the
blinking colon is not visible.
NOTE: The blinking colon is indicated by in this manual.
3.3.1.2
DATA ENTRY STATUS
Indicated by blinking equal sign (=) on bottom line of LCD; the power supply is waiting for data
to be entered. A command will not be accepted (accompanied by brief audible buzz). Enter new
value (the
key erases data entered). Press ENTER to accept new setting, or CLEAR to exit
without changing setting.
NOTE: The blinking equal sign is indicated by in this manual.
Содержание ABC 10-10DM
Страница 2: ......
Страница 6: ......
Страница 14: ...viii ABC 040104 FIGURE 1 1 ABC SERIES POWER SUPPLY...
Страница 18: ...1 4 ABCOPR040104 FIGURE 1 1 ABC SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING...
Страница 19: ...ABCOPR040104 1 5 FIGURE 1 2 ABC POWER SUPPLY AND RA 71 RACK ADAPTER OUTLINE DRAWING...
Страница 20: ...1 6 ABCOPR040104 FIGURE 1 3 TWO ABC POWER SUPPLIES AND RA 72 RACK ADAPTER OUTLINE DRAWING...
Страница 24: ......
Страница 58: ......
Страница 64: ......
Страница 94: ......
Страница 96: ...FOLD HERE Please place stamp here KEPCO INC 131 38 SANFORD AVE FLUSHING NY 11352 USA CUT HERE...