background image

 

Product Manuals/Man-1099_Syncro_Si_Status_Unit_05

 

 

3. Installation 

 

Installation of the units should be carried out by qualified personnel only. The electronic components within the units are 

vulnerable to physical damage and damage by electrostatic discharges.   
It is advisable to wear a wrist strap designed to prevent the build-up of static charges within the body, before 

handling any electronic circuit boards. 
Never insert or remove boards or components with the power on. 
Mounting the boxes 
The site chosen for the location of the units should be clean and dry and not subject to shock or vibration. The temperature 

should be in the range -5° to +35° C, the humidity should not exceed 95%. 
Remove the front plate by taking out the two fixing screws and put them in a safe place for re-fitting later. 

 

Remove knockouts from the top and or back of the box in the positions at which cables will enter. 

 

Using the box as a template, mark the position of the fixing holes, ensuring that the wall is flat at the chosen location. Screws 

or bolts of a minimum of 5mm diameter and 40mm long must be used to mount the enclosure in all mounting positions. 
 

 

 

 

After the box is firmly fixed, remove any knockout blanks and dust or swarf caused by drilling and 

fixing the box.

 

4. Cabling 

 

Cables should be brought into the cabinet using the knockouts provided and where necessary, using 

couplers to maximise the space within the enclosure. Use the knockouts closest to the terminating 

position for each cable, to ensure cable length within the enclosure is kept to a minimum. 
Ensure that only the numbers of knockouts are removed to meet the cable termination 

requirements, as any additional apertures in the enclosure will compromise the IP30 ingress 

protection. 
Brass inlet bushings or cable glands should be used to maintain insulation and to ensure EMC 

compliance. t 
The screen or drain wires should be bonded to earth via metal cable glands. 
The maximum size of cable, which can be terminated, is 2.5

2

 mm. 

The communications protocols are highly immune to noise but sensible segregation from known 

noise generating sources such as mains cables is recommended. 

Отзывы: