General Trouble
The General Trouble LED illuminates during all trouble conditions. The LED also lights when the
Enable Access key has been removed while in Access Level 3.
Lamp Test
All LED indicators can be tested at any time by pressing the Lamp Test button. Access Level 2 is not
required to perform the Lamp Test. The internal buzzer of the fire control panel can be silenced at any
time by pressing the Buzzer Silence button. Access Level 2 is not required to silence the internal
buzzer.
Test Mode
To operate Test Mode:
1
Turn the Enable Access key to the right to enter Access Level 2.
Code t1 is displayed on the Mode LED.
The figure below illustrates code t1 on the Mode LED:
Figure 4- 6
Code t1 on the Menu
2
Press Select (+1) to scroll through codes t1-t8 for testing.
Codes t1-t8 correspond to zones Z1-Z8.
3
Press Enter to program test codes in the t1-t8 range.
Test mode codes that are programmed for testing contain a flashing dot in the lower-right-corner
of the Mode LED.
The Test Mode On LED and the Alarm In Zone LED are lit to confirm the test mode condition.
Mode
Enable Access
1
www.acornfiresecurity.com
www.acornfiresecurity.com