background image

Man-1128_K25400_series_Power_Supply_Manual_15 

Page 

8

 of 

20

 

3.4.5 Fault output contact connections 

 

A volt free contact rated at 30V DC and 1 Amp is available 

for connection to other systems. 

 

This contact will operate upon any of the fault conditions 

listed in section 4. 

 

The contact positions shown here are with mains 

and battery connected and with no fault conditions 

on the power supply. 

 

 

 

3.4.6 Battery Connections 

 

Batteries of even very small capacity are capable of 

delivering very high currents which can cause fire or 

injury. Battery connections must therefore be made using 

extreme caution

As supplied, power supplies have  battery leads already 

wired to the battery terminals on the circuit board. These 

leads are coloured red for + and black for – and are fitted 

with standard ¼ inch  push on, spade connectors suitable 

for batteries of up to 12Ah capacity.  

Larger capacity batteries have screw on terminals and the 

standard battery leads will need to be replaced with the 

ones supplied in the accessory pack.   Take care that the 

red and black wires are connected to the correct terminals when replacing battery leads, a wrong connection can be 

dangerous and can cause damage. 

As this is a 24-Volt system, there will be two 12 volt batteries which need to be connected in series. This is done using 

the jumper link provided. 

To optimise the service life of the batteries, the battery charger output voltage varies with temperature. To enable 

optimum temperature compensation, the flying lead temperature sensor should be attached to one of the batteries as 

shown in the diagram in section 9 of this manual. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J5

24V

DC

DC

RTN

NORMALLY OPEN

COMMON

NORMALLY CLOSED

Содержание K25000 Series

Страница 1: ...Man 1128_K25400_series_Power_Supply_Manual_15 Page 1 of 20 K25000 KD25000 Series Fire Alarm Power Supplies Installation Commissioning and Operating Manual Man 1128 Issue 15 October 2019...

Страница 2: ...Load Connections Terminal Block 6 3 4 2 Load Connections Ribbon Cable 6 3 4 3 Load connections optional dual transmission path PCB fitted 7 3 4 5 Fault output contact connections 8 3 4 6 Battery Conn...

Страница 3: ...dels 2 5Amps 1 0 A for battery charging Maximum ripple 1 Volt Imax a Rated maximum output current which can be supplied continuously K25400 models 4A K25250 models 2 5A Imax b Rated maximum output cur...

Страница 4: ...ing positions It should be positioned in an accessible place as agreed with the end user The unit should not be mounted in another enclosure or near sources of excessive heat Cables should be connecte...

Страница 5: ...tage wiring such as 24V supply wiring and battery leads Ensure that all wires are fitted into the terminals without any exposed lengths or strands which may give rise to exposure to electrical shock T...

Страница 6: ...y be used to connect to the load and fault signals See below When used in the K25000 series boxed power supplies the load connection terminals detailed in 3 4 1 above must be used as the primary power...

Страница 7: ...e alarm control and indicating equipment with two separated 24V DC inputs is compatible with these power supply units Care must be taken to connect the polarity the correctly on the RPSM2 PCB to on th...

Страница 8: ...d red for and black for and are fitted with standard inch push on spade connectors suitable for batteries of up to 12Ah capacity Larger capacity batteries have screw on terminals and the standard batt...

Страница 9: ...ply with the requirements of EN54 4 this switch setting must not be used when the power supply is being used to power fire alarm detection and control equipment Battery disconnected fault warning disa...

Страница 10: ...harge current is low while the charger output current is at the maximum limit EARTH FAULT The 24V DC output has a low resistance path to earth AC NORM Mains power is connected 5 Commissioning Once all...

Страница 11: ...batteries consistently operating in higher ambient temperatures should be replaced more frequently Batteries with a manufacturing date older than 6 months are not recommended for use with this equipm...

Страница 12: ..._Power_Supply_Manual_15 Page 12 of 20 8 Power Supply Unit Dimensional Drawings 385mm 285mm POWER ON POWER FAULT 90mm KD25250M2 and KD25250M2 WT 385mm 520mm POWERON POWERFAULT 110mm KD25250M3 KD25400M3...

Страница 13: ...an 1128_K25400_series_Power_Supply_Manual_15 Page 13 of 20 POWER ON POWER FAULT 500mm 355mm 105mm KD2540003 KD2525003 K2540003 and K2525003 POWER ON POWER FAULT 500mm 400mm 190mm KD2540015 and K254001...

Страница 14: ...lead thermistor must be affixed to one of the batteries using Scotch 27 Glass Cloth Electrical Tape or equivalent A suitable piece of this tape is supplied holding the temperature sensor to the power...

Страница 15: ...ower supply output cables Extra Low voltage wiring Cable for low voltage wiring should be a minimum size of 1 0mm2 and rated for at least 30V DC Keep all Extra Low voltage wiring separate from mains w...

Страница 16: ...power supply unit 7 Carefully remove the two M4 screws on the left side of the power supply unit ensuring any washers ring crimps are kept safe These screws are located in the top left corner of the...

Страница 17: ...he power supply Note When the power supply is removed from the panel enclosure it is possible to view the link location on the circuit board through an aperture in the outer cover at the top of the po...

Страница 18: ...Man 1128_K25400_series_Power_Supply_Manual_15 Page 18 of 20...

Страница 19: ...Man 1128_K25400_series_Power_Supply_Manual_15 Page 19 of 20...

Страница 20: ...Man 1128_K25400_series_Power_Supply_Manual_15 Page 20 of 20 Man 1128...

Отзывы: