- 58 -
Does the cold-air come out
of the top of the main duct?
Yes
No
Check the
Damper itself
Enter the TEST 2 MODE
Does not cold-air come out
of the top of the main duct?
No
Yes
Checking Damper itself
Is the resistance
Values between (1) & (4),
(2) & (3) like as below?
(1)RD
(2)WH
(3)BL
(4)YL
No
Yes
373 ~ 456 ½
(1) To (4)
373 ~ 456 ½
(2) To (3)
Result
Test Point
Replace
Damper
(Position
No:120A)
After reset the unit, take steps to PWB as
follows for temperature compensation.
1. In the case of EBR419564
: Compensate with Jump wire cutting
* Cutting of jumper wire
-1.0 deg
JCR4
Cutting both jumpers affords a 2¼
temperature compensation
-1.0 deg
JCR3
Temp.
Compensation
JUMP
WIRE
Check the
Damper itself
Resistance of Damper