K410068602008-00 / 09.2018
73
KHS cable list
This list of cables only shows examples
of applications. The exact design of the
cables in questions must be carried out
on site by the planner on the basis of
the ambient conditions (temperature,
frequency, routing type, mechanical
load).
* Possible cable type for fixed routing, without mechanical load
** Shielded cable lead
According to VDE 0815: The specification of signal transmission cables with
respect to the diameter is specified in mm.
Designation
Art.-No.
Cable cross-section /
diameter
Max. cable
length
Cable type*
[-]
[-]
[mm²] [mm]
[m]
[-]
KHS quarter turn stop
valve PLUS with spring
reset servo drive (24 V)
686 01 015…032
3 x X mm²
(power supply)
+
2 x 2 x 0.80 mm **
(position feedback)
NYM-J
+
J-Y(ST)Y
KHS quarter turn stop
valve with servo drive
(24 V)
686 00 015…032
5 x X mm²
(power supply)
+
2 x 2 x 0.80 mm **
(position feedback)
NYM-J
+
J-Y(ST)Y
KHS quarter turn stop
valve PLUS with spring
reset servo drive (230V)
3 x 1.50 mm²
1000
NYM-J
KHS quarter turn stop
valve with servo drive
(230 V)
686 04 015…032
5 x 1.50 mm²
1000
NYM-J
KHS free drain with
overflow sensor
688 00 020...032
2 x 2 x 0.80 mm **
1000
J-Y(ST)Y
Kemper CONTROL PLUS
flow measurement valve
Vortex principle
138 4G 015…050
4 x 2 x 0.80 mm **
300
J-Y(ST)Y
Kemper CONTROL PLUS
flow measurement valve
Vortex principle
138 6G 015…050
4 x 2 x 0.80 mm **
300
J-Y(ST)Y
KHS flow and
temperature sensor
Pt 1000
628 0G 015...050
629 0G 015...050
2 x 2 x 0.80 mm **
1000
J-Y(ST)Y
Leakage water sensor
620 00 00100
2 x 2 x 0.80 mm **
500
J-Y(ST)Y
CAN bus cable
The application is based on
the ISO 11898 international
standard.
1 x 2 x 0.34 mm² **
1 x 2 x 0.50 mm² **
1 x 2 x 0.75 mm² **
300
500
1000
CAN bus cable
686 05 015…032
685 15 032…050
700 (X=1,50)
1000 (X=2,50)
250 (X=1,50)
450 (X=2,50)