background image

Specification and Operating Instructions

Wiring Diagram

ETDT1510I_090320

KLTIMER

SUPPLY

POWER

OUTPUT

Description

The timer controller acts on a relay connecting it for a 
programmable time interval.

Timer features include soundwarning when the countdown expires, 
count units in seconds or minutes 

abort by the keyboard, remote 

countdown input, manual control to switch ON/OFF the output, 
and 

maximum interval limit.

Installation

(seconds are allways indicated by 

a blinking led)

countdown 

programmable 

Model references

NOTE: Unit must be mounted away from vibration, impacts, 
water and corrosive gases.

Cut hole in panel 71 x 29 mm (2.80 x 1.14 inches)

 Apply silicone (or rubber gasket) around the perimeter of the hole 

to prevent leakage.

 Insert unit into hole of panel.
 Slide removable fitting clips onto unit from the back until secure to 

panel.

 Wiring diagram is displayed on the top of the unit

Maintenance, cleaning and repair

After final installation of the unit, no routine maintenance is 
required.

The model reference is given by: KLT11TIM   - WY.

Where each sufix can take the following values:

W  Display Color

R=Red, G=Green, B=Blue

Y   Supply Voltage

230=230Vac, 110=115Vac
24=24Vac/dc, 12=12Vac/dc

• 


Clean the surface of the display controller with a soft and damp 
cloth. Never use abrasive detergents, petrol, alcohol or solvents.
All repairs must be made by authorised personnel.

Technical Data

Storage temperature

-20ºC to 80ºC  (

-

4 to 176ºF)

Operating temperature

0ºC to 70ºC (32 to 158ºF)

Time resolution

Supply voltages

115Vac±10%, 230Vac±10%, 24Vac/dc±10%, 12Vac/dc±10%

Supply powers

4VA (230V)

1 sec 

Displays

3-digit

Output

SPST Relay Resistive load 16A
1HP 240Vac -- 10FLA, 60LRA 240Vac

Dimensions

Front 77 x 36 mm (3.03 x 1.42 inch) 
Depth 62 mm ( 2.44 inch)

Front Protection

IP64 

Back Protection

IP20 

KLTIMER Timer

 

Controller

3  4  5 6  7  

OUT

1  2

REMOTE

COUNTDOWN INPUT