WARNING!
Danger to persons by electric shock!
●
Only supply the device with power from voltage sources having protective
extra-low voltage (e.g. SELV or PELV acc. to IEC 61131-2)
●
Only connect voltages and circuits which are safely separated from dan-
gerous voltages (e.g. by means of sufficient insulation) to connections,
terminals or interfaces up to a rated voltage of 50 V.
Ethernet
Fig.14-5:
Connection diagram for Ethernet: KeTop T10 via junction box JB 001
Information
Point-to-point connections between KeTop and PLC require a crossed cable.
14.2.4
Shielding inside the Control Cabinet
In many cases, several interference sources exist in the control cabinet, such
as servo drive modules, transformers, contactors and relays. Therefore it is
necessary to continue the cable shield from the connector shell (control cabi-
net) up to the PLC (continuous connection from handheld terminal up to PLC).
KeTop T10
Accessories
© KEBA 2014
Project engineering manual V1.02
49