Connections and wiring

Project engineering manual V1.06

44

© KEBA 2021

6.7.4

Cable and plug specification

For details, refer to the system manual.

6.8

Serial interface

The module offers 1 configurable serial interface (X51A SI) at the front side,
which can be used in different modes. The mode can be set on the software
side.

6.8.1

RS-232-C interfaces

Via RS-232-C interface participants can comminicate by point-to-point con-
nection. The wire has to be shielded.

6.8.1.1

Pin assignment

Fig. 6-31: Industrial Mini I/O socket type 2

RS-232-C

Pin-No.

Signal designation

Input/output

1

TxD

Transmit Data

Output

2

RTS

Request To Send

Output

3

RxD

Receive Data

Input

4

n.c.

Not connected

---

5

n.c.

Not connected

---

6

CTS

Clear To Send

Input

7

n.c.

Not connected

---

8

GND

Ground (Signal ground)

---

6.8.1.2

Bus termination

Information

The RS-232-C bus does not require bus termination.

To deactivate bus termination the DIP switch (S1) on the front of the module
is set (see "Serial interface configuration").

Содержание KeControl CP 50 Series

Страница 1: ...KeControl CP 503 A CP 505 A D K CP 507 A C CPU module Project engineering manual V 1 06 Translation of the original instructions...

Страница 2: ...rther technical developments Details presented may be subject to correction All rights reserved KEBA Industrial Automation GmbH Reindlstra e 51 4040 Linz Austria 43 732 7090 0 43 732 7309 10 keba keba...

Страница 3: ...ious chapters 7 segment display Micro SD card technical data hasl 1 03 10 2021 Various chapters Expansion interface created new structure of adding modules expansion bus updated change to new company...

Страница 4: ...CP 503 A CP 505 A D K CP 507 A C Project engineering manual V1 06 4 KEBA 2021...

Страница 5: ...structions 13 2 3 Safety instructions for device maintenance 14 2 4 ESD information 14 3 Description of the module 15 3 1 Front view 15 3 2 Side view 16 3 3 Bottom view 18 3 4 Storage media 18 3 4 1 M...

Страница 6: ...Removing expansion modules 37 5 8 Air conditioning and ventilation 38 5 8 1 Use of air filters 38 6 Connections and wiring 39 6 1 Power supply 39 6 1 1 Connection example 40 6 2 EMC and wiring guidel...

Страница 7: ...rrors 63 8 6 Watchdog 63 8 7 Failure of power supply 63 8 8 Battery monitoring system 63 8 9 Temperature monitoring 64 9 Diagnosis 65 9 1 LEDs 65 9 2 7 segment display 65 9 3 State report 65 9 4 Crash...

Страница 8: ...76 12 5 Interfaces 77 12 6 Dimensions weight 78 13 Directives standards and regulations 79 13 1 EU Directives 79 13 2 Standards for checking the conformity 79 13 3 Other standards 79 13 4 Regulations...

Страница 9: ...ith the following skills Target group Knowledge and skills pre requirement Project engineer Basic technical training University of Applied Science University level engineering degree or corresponding...

Страница 10: ...pproved devices The CP 50x x has been developed manufactured tested and documented observing the relevant instructions and standards Therefore provided that the instructions and safety precautions are...

Страница 11: ...Maintenance Technical data 1 4 2 Not contained in this document Programming instruction Application diagnosis Firmware description 1 5 Documentation for further reading Name Target group Provided sys...

Страница 12: ...or seri ous bodily injury if the corresponding precautions are not taken CAUTION means that if the corresponding safety measures are not taken a potentially hazardous situation can occur that may resu...

Страница 13: ...Use in environments with harmful solutions steams or radiations Use in non stationary applications The CP 50x x is not designed for safety relevant control tasks e g shutdown in case of an emergency...

Страница 14: ...t discharges are so low that they are not noticeable However they can nevertheless put unprotected electronic components at risk or even destroy them Therefore any handling with open electronics is on...

Страница 15: ...nge performance within the KEBA automation system 3 1 Front view Fig 3 1 Front view 1 Locking hooks expansion module 2 USB interface 3 DVI interface 4 Ethernet interfaces 5 Serial number and DataMatri...

Страница 16: ...le Project engineering manual V1 06 16 KEBA 2021 3 2 Side view Fig 3 2 Left side view 1 Locking hooks expansion module 2 Area for type plate printing 3 Area for connection diagram print ing 4 Mounting...

Страница 17: ...ing manual V1 06 17 KEBA 2021 Fig 3 3 Right side view 1 Recesses for locking 2 Lock of the input output module 3 Area for type plate printing 4 Area for symbol printing 5 Mounting rail locking 6 KeBus...

Страница 18: ...operated with the following storage media Micro SD card 3 4 1 Micro SD card The CP 50x x uses a Micro SD card that contains the operating system It is possible to insert and remove the Micro SD card...

Страница 19: ...ed as follows 1 Turn off the power supply 2 Gently push the Micro SD card into the Micro SD slot until it clicks into place audible click Insert in the proper direction Fig 3 5 Inserting the Micro SD...

Страница 20: ...e pends on the module Fig 3 7 Example type plate 1 Manufacturer s address 2 Manufacturer 3 Product group 4 Product designation 5 Technical data voltage 6 Ambient temperature 7 Country of manufacture 8...

Страница 21: ...8 1 Micro SD card The recommended Micro SD card can be requested and ordered from KEBA Designation Description Order no XC 540 C 0000 Micro SD card 2 GB 112917 XC 540 D 0000 Micro SD card 4 GB 112918...

Страница 22: ...nector Type II 1 2201855 1 company TE Connectivity The technical data is provided in the manufacturer s technical data sheet for the plugs that are used 3 8 4 Industrial Mini I O cable The appropriate...

Страница 23: ...the operating status after start up The decimal point serves as load display A flashing decimal point sig nals that the CPU load is in the allowed range If the decimal point stops blinking then the C...

Страница 24: ...s are displayed by flashing in the 7 segment display Once the initial status has been reached again this will be indicated normally again Long keystrokes are used to execute a command and to change in...

Страница 25: ...isplay Meaning Dark No power supply or error free transmission Red Bus Off Faulty transmission with activated CAN channel e g cable disconnected faults on cable faulty slave etc 4 6 EtherCAT status LE...

Страница 26: ...e operating and load voltage supplies before carrying out as sembly installation or maintenance work 5 2 Mounting rail A steel rail TS 35x7 5 is to be used as mounting rail for the device For the sake...

Страница 27: ...4 Space requirements The module housing has ventilation slots for heat dissipation Caution The ventilation slots must be kept free at all costs The cooling system and housing of the module are designe...

Страница 28: ...ace for the air circulation of the module At least 30 mm above and below the module 5 5 Installing the module Caution Permissible installation position The mounting rail must be installed so that the...

Страница 29: ...ut it on the mounting rail fixture 2 3 Press the lower half of the module onto the mounting rail 3 4 Lock all of the mounting rail locks one after the other 4 5 Use the end brackets to secure the modu...

Страница 30: ...e module to release it from the mounting rail 2 6 Remove the module from the mounting rail 3 The module is dismantled 5 7 Adding modules Input output modules and expansion modules can be added to the...

Страница 31: ...x x specified in the technical data see Technical data Information In order to calculate the number of input output modules that can be connected on the right the respective performance values specifi...

Страница 32: ...end bracket 3 Release the lock on the right side of the module to which the input out put module is to be added by pushing it up Fig 5 16 Releasing the lock 4 Install the input output module to be ad...

Страница 33: ...t output modules 6 Secure the lock on the right side of the already mounted module by pushing it down Fig 5 18 Securing the lock 7 Secure the end bracket on the mounting rail The input output module i...

Страница 34: ...f the plug connector on the left side of the already installed module 5 Install the expansion module to be added on the mounting rail and lock it see 5 5 Installing the module 6 Slide the expansion mo...

Страница 35: ...ion module 7 Secure the lock on the right side of the new added expansion module by pushing it down Fig 5 21 Securing the lock 8 Secure the end bracket on the mounting rail The expansion module is add...

Страница 36: ...oved by pushing up Fig 5 22 Releasing the lock 4 Slide the input output module to the right until the hooks have disen gaged from the recesses of the module to the left Fig 5 23 Removing input output...

Страница 37: ...2 Remove the end bracket 3 Release the lock on the right side of the expansion module to be re moved by pushing it up Fig 5 24 Releasing the lock 4 Slide the expansion module to the left until the rec...

Страница 38: ...erature of the module If this cannot be guaranteed through natural heat dissipation an air conditioning of the control cabinet must be provided The specified required free space above and below the mo...

Страница 39: ...supply of the CP 50x x Power supply of the CP at the terminal X00A The CP 50x x is supplied with voltage via the terminal X00A The terminal is located on the lower right on the front side CAUTION Fire...

Страница 40: ...equipment an the female connectors used Max load current and required heat dissipation through the connected wire at maximum ambient temperature Permissible voltage drop for error free operation of t...

Страница 41: ...front side The USB port is used to connect removable media for exam ple during maintenance or peripherals e g keyboard mouse It is however not suited for unmonitored continuous operation as the connec...

Страница 42: ...odule and are used for communication with non real time networks LAN and or visualization systems 6 6 1 Pin assignment Fig 6 28 Pin assignment RJ45 socket Pin no Signal designation Input output 1 MX0...

Страница 43: ...ion The connection SGND Signal Ground and GND optional ground connec tion are connected internally The designation was chosen according to the norm CiA CAN in Automation 6 7 2 Bus termination To activ...

Страница 44: ...participants can comminicate by point to point con nection The wire has to be shielded 6 8 1 1 Pin assignment Fig 6 31 Industrial Mini I O socket type 2 RS 232 C Pin No Signal designation Input outpu...

Страница 45: ...output 1 A Transmit Data Output 2 B Transmit Data Output 3 A Receive Data Input 4 n c Not connected 5 n c Not connected 6 B Receive Data Input 7 n c Not connected 8 GND Ground Signal ground 6 8 2 2 Bu...

Страница 46: ...at the bus due to cable routing To select a particular bus termination the DIP switch S1 on the front of the module is set see Serial interface configuration 6 8 2 3 Connection example Information It...

Страница 47: ...For details refer to the system manual 6 8 3 RS 485 A interfaces Several participants can communicate via the RS 485 A bus at which the maximum number of participants is limited to 32 The wires to oth...

Страница 48: ...f the bus termination beginning end is done by an external par ticipant the termination must be deactivated for the CP 50x x The bus termination must take place at the bus end i e at the first and las...

Страница 49: ...is only allowed once per RS 485 A bus The resistors Rpull up and Rpull down pull the RS 485 A bus to a defined level even if no data is sent by the participants To select a particular bus termination...

Страница 50: ...r termination Fig 6 37 Example Resistor termination 1 CP 50x x 2 External participant 3 Other participants 4 Transmitter receiver Bus termination with resistor termination without fail safe wiring Fig...

Страница 51: ...ple AC termination 1 CP 50x x 2 External participant with AC termi nation 3 Other participants 4 Transmitter receiver Fig 6 40 Example AC termination 1 CP 50x x 2 External participant with resistor te...

Страница 52: ...pin as signment KEBA does not perform any tests for the correct functionality of operating devices from third party manufacturers 6 9 1 Pin assignment Fig 6 41 Pin assignment DVI socket Pin no Design...

Страница 53: ...PCIe lanes and sync lines provided by the CP 50x x see Technical data Each extension module requires its own line on the extension bus A line cannot be used jointly by several extension modules This m...

Страница 54: ...information on configuration 7 1 CAN configuration The termination of the CAN interface CAN is activated ON or deactivated OFF via DIP switch S1 ON OFF position of the switches The illustration shows...

Страница 55: ...he termination of the serial interface SI is activated AC R R without fail safe or deactivated OFF with the DIP switch s1 ON OFF position of the switches The illustration shows the position of the swi...

Страница 56: ...operating system is located in the re spective slot of the CPU module 8 1 1 Display during start up The progress in each stage is signaled via the 7 segment display If an error occurs during startup t...

Страница 57: ...e controller is in error state Exception Pressing the CTRL key toggles between the operating states 8 3 7 segment display The CP 50x x has a 7 segment display During operation the current status is sh...

Страница 58: ...Copy last status report The last status report is copied to the root directory of the plugged USB stick The process may take some time Error while copying the data e g USB stick disconnected during c...

Страница 59: ...eport copy The crash report is copied to the root directory of the plugged USB stick The process may take some time Error while copying the data e g USB stick disconnected during copying no space left...

Страница 60: ...continue with short key press Action execute with long key press Controller is in RUN state Go to action stop controller Stop controller The controller goes to STOP state Stop controller The controll...

Страница 61: ...ck The process may take some time Error while copying data e g USB stick removed during copying no space left on USB stick etc The error must be confirmed by a long keystroke EXCEPTION Displayed state...

Страница 62: ...must be confirmed by a long keystroke Copy last SysStatus report The last SysStatusreport is copied to the root directory of the plugged USB stick The process may take some time Error while copying d...

Страница 63: ...alog outputs are set to 0 V The CPU continues to run for diagnostics purposes The CPU watchdog monitors the principal function of the CPU and runs independent from the IO watchdog After the CPU watchd...

Страница 64: ...System manual 8 9 Temperature monitoring The temperature of CP 50x x is checked via internal sensors If the tempera ture violates an alarm limit a message will be sent and the application has the poss...

Страница 65: ...e file is stored in the log directory Please send this to your contact at KEBA or sup port a keba com 9 2 7 segment display The CP 50x x has a 7 segment display for signalling status information and e...

Страница 66: ...turn into the previous main operating mode 9 4 Crashreport If a system error e g unhandled exception occurs a crash report file is automatically created and saved to a removable storage device of the...

Страница 67: ...f the battery is not replaced when there is a warning message the data in SRAM and the real time clock setting can be lost if the supply power is interrupted To prevent loss of data the power supply o...

Страница 68: ...oving the battery tray 2 Remove the old battery from the battery tray Inserting the battery 1 Insert the new battery in the battery tray Pay attention to polarity Fig 10 45 Inserting the battery in th...

Страница 69: ...peration 8 6 years for 24 7 operation 8 years for 24 7 op eration 6 9 years for 24 7 operation Information Since the data is a typical lifetime L10 it is recommended that the fan be replaced already w...

Страница 70: ...r proceed as follows 1 Disconnect the voltage supply 2 Loosen the screws with the screwdriver 3 Remove the fan cover 4 Disconnect the connection cable To do this carefully pull the plug up wards with...

Страница 71: ...ring manual V1 06 71 KEBA 2021 2 Attach the fan cover to the housing Caution Possible damage to property by pinching the fan cables Do not pinch the cables when attaching the fan cover 3 Tighten the f...

Страница 72: ...ium including all net work settings are backed up KeStudio U4 offers the possibility to install the created backup as a simula tion on the PC For more information see online help of KeStudio U4 To sav...

Страница 73: ...ry is changed to the name of the directory of the desired backup The file is saved and when a backup is restored this directory is now used To restore the backup proceed as follows 1 Connect the servi...

Страница 74: ...ribution to protecting our environment by reusing renewing and recycling materials and old appliances 11 2 Disposal of the battery Caution When disposing of batteries the regulations for proper dispos...

Страница 75: ...er1 0 C to 50 C CP 505 x 0 C to 55 C CP 505 x with additional output power1 0 C to 45 C CP 507 x 0 C to 60 C Storage temperature 40 C to 70 C Relative humidity of air 10 to 95 non condensing Vibration...

Страница 76: ...erface is 20 W or 4 5 W respectively CP 507 x Nominal supply voltage 24 V DC from the front rated voltage toler ance 19 2 V DC to 30 V DC in acc with EN 61131 2 Inrush current Max 10 A Total power con...

Страница 77: ...Quantity 1 Type microSD CAN interfaces Quantity 1 Data transmission rate 125 kbit s bis 1 Mbit s configurable via soft ware Terminating resistor Yes configurable via DIP switch on front Galvanic isola...

Страница 78: ...PCIe lanes 1 SATA 1 USB 2 0 2 Slave sync lines 2 Master sync lines 4 12 6 Dimensions weight Fig 12 47 Dimensions Height H1 Height with lock 126 5 mm H2 Height without lock 121 mm H3 Height to mounting...

Страница 79: ...andards Immunity standard for industrial environments EN IEC 61000 6 4 2019 Electromagnetic compatibility EMC Part 6 4 Generic standards Emission standard for industrial environments Check of the conf...

Страница 80: ...t 13 4 Regulations Regulation EG No 1907 2006 REACH EU chemicals regulation Information Information obligation from REACH regulation To meet the information obligation according to article 33 of REACH...

Страница 81: ...P 505 A D K CP 507 A C EU Declaration of conformity Project engineering manual V1 06 81 KEBA 2021 14 EU Declaration of conformity The declaration of conformity of this product is available on request...

Страница 82: ...forderlich ist die in Gro britannien England Wales und Schottland auf den Markt gebracht werden Authorised representative is KEBA Ltd Aston Court Frederick Place Kingsmead Business Park High Wycombe H...

Страница 83: ...life 67 Type 67 Battery slot Position 18 Bus termination 55 C CAN interface Bus termination 43 CAN status LEDs 25 Connection 43 Pin assignment 43 Position 15 Technical data 77 Codes Data matrix code 2...

Страница 84: ...cing 69 Service life 69 Fan cover Inserting 70 Oder number 22 Removal 70 Feldbus interface Technical data 77 G Gigabit Ethernet interface Pin assignment 42 Graphic interface Connection 52 Pin assignme...

Страница 85: ...unting rail Position 18 Locking hooks Position 15 16 M Micro SD card 18 Inserting 19 Removing 19 Micro SD card slot Position 15 Mini I O plug Plug Connector Type II 22 Module address 32 Module bus 78...

Страница 86: ...Termination 45 RS 485 A 47 AC termination 51 Bus termination 48 Configuration 54 No termination 49 Pin assignment 48 Resistor termination 50 Termination 48 S Serial interface Position 15 Technical da...

Отзывы: