E10
Configuration
V1.00
22
© KEBA 2023
Register
Description
262 (
0x0106
)
4th octet (e.g. 55)
Subnet mask (registers 263 - 266)
263 (
0x0107
)
1st octet (e.g. 255)
264 (
0x0108
)
2nd octet (e.g. 255)
265 (
0x0109
)
3rd octet (e.g. 255)
266 (
0x010A
)
4th octet (e.g. 0)
DHCP server (register 267)
267 (
0x010B
)
0: DHCP not activated
1: DHCP activated
The settings are applied after restarting the device.
9.4
Read-only flag (register 268)
The read-only flag can be set by writing the value 1 to Modbus register 268
(
0x010C
). If the read-only flag is set, no other configuration can be per-
formed. All Modbus configuration registers only allow read access (function
code 0x3). Write access leads to Modbus exception code
0x03 Illegal
Data Value
.
To deactivate the read-only flag, the device must be reset to factory settings.
9.5
Error codes
The following error codes can occur:
Error code
Description
0x02 Illegal
Data Access
A client tries to read unspecified registers.
0x03 Ille-
gal Data
Value
●
Read or write access to a register that is not supported
●
Write access to parameters outside the permitted range
●
Write access to data block with activated read-only flag
0x04 Slave
Device
Failure
The device is in an error state
Содержание KeContact E10
Страница 1: ...KeContact E10 Energy meter Installation manual V 1 00 Original instructions...
Страница 30: ...E10 Declaration of conformity V1 00 30 KEBA 2023 15 Declaration of conformity...
Страница 31: ...E10 Declaration of conformity V1 00 31 KEBA 2023...
Страница 33: ......
Страница 34: ...KEBA Energy Automation GmbH Reindlstra e 51 4040 Linz Austria www keba com...