E10
Configuration
V1.00
21
© KEBA 2023
9
Configuration
The device can be configured using the Modbus TCP protocol. A detailed
description of the Modbus protocol can be found in the official Modbus speci-
fication (see http://www.modbus.org).
The configurable values are described in this chapter.
mDNS
The device offers the
_mbap._tcp
service type and can be found under the
instance name
MB_TCP[Seral number]
. The product name and unit ID can
be read out using the instance name.
9.1
Measuring interval (register 256)
The measuring interval can be set using Modbus register 256 (
0x0100
). The
following values can be set:
Value
Description
1
100 ms
2
200 ms (default)
3
500 ms
4
1000 ms
9.2
Split-core current transformer (register 257)
The split-core current transformer used can be set using Modbus register
257 (
0x0101
). The following values can be set:
Value
Description
0
CT1
1
CT2
2
CT3
3
CT4
9.3
Network configuration (registers 259 - 267)
The network configuration can be performed using the following Modbus
registers:
Static IP address (registers 259 - 262)
Register
Description
259 (
0x0103
)
1st octet (e.g. 192)
260 (
0x0104
)
2nd octet (e.g. 168)
261 (
0x0105
)
3rd octet (e.g. 1)
Содержание KeContact E10
Страница 1: ...KeContact E10 Energy meter Installation manual V 1 00 Original instructions...
Страница 30: ...E10 Declaration of conformity V1 00 30 KEBA 2023 15 Declaration of conformity...
Страница 31: ...E10 Declaration of conformity V1 00 31 KEBA 2023...
Страница 33: ......
Страница 34: ...KEBA Energy Automation GmbH Reindlstra e 51 4040 Linz Austria www keba com...