![KEB Combivert R6 Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/keb/combivert-r6/combivert-r6_instruction-manual_660412053.webp)
53
Annex A
A.3
Decoupling diodes
Use decoupling diodes when using the R6 as regenerative unit only, to avoid that the con-
nected inverters cannot be supplied via the regenerative unit. Appropriate decoupling diodes
are defined for the different sizes.
A.3.1 Assignment
R6-N Material number
Type
Volume
Ta [°C]
Th [°C]
Rha [K/W]
15
0090147-3500
1600 V / 80 A
2
45
90
1.50
19
0090147-4101
1600 V / 120 A
2
45
90
0.84
25
0090147-6009
1600 V / 560 A
2
45
90
0.19
29
0090147-6009
1600 V / 560 A
2 x 2
45
90
0.09
Legend
Ta: maximum ambient temperature
Th: maximum heat sink temperature
Rha: required thermal resistance of the heat sink at rated operation
(thermal value of the thermal compound ≥ 0.5 W/(m*K))
A.3.2 Dimensions of the decoupling diodes
Material number
Connection
Dimensions
0090147-3500
1 (anode)
2 (cathode)
or
3 (anode)
1 (cathode)
continued on the next page