Connection of the control board version N
4.5
Connection of the control board version N
4.5.1 Assignment of the control terminal strip X2A
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
X2A
Core cross-section 0.14…1.5 mm², tightening torque 0.5 Nm
PIN Function
Name
Default
Description
Specifications
10 24V input
Uin
External supply of the control
board
21.6…26.4 V DC
/ 1 A
11 24V ground
COM
Reference potential: 24V input
12 Digital input 1
ST
Control release / reset
Ri: 4.4 kΩ
13 Digital input 2
I1
Set selection
programmable
14 Digital input 3
I2
Set selection
programmable
15 Digital input 4
I3
Ext. error
programmable
16 Mass
COM
Reference potential
17 24 V output
Uout
Voltage supply for in and
outputs
approx. 24 V /
max. 100 mA
18 Mass
COM
Reference potential
19 Digital output 1
O1
DC > 600V
Transistor output (DC >
CP.19)
I
max
: 25 mA
20 Digital output 2
O2
Error message Transistor output (error mes-
sage)
I
max
: 25 mA
21 Analog output
ANOUT
Difference to mains frequen-
cy (CP.18)
0…±10 V / max.
5 mA
22 24 V output
Uout
see terminal 17
23 Mass
COM
Reference potential
24 Relay 1 / NO contact
RLA
Ready for
operation (no
error)
Relay output
Ready signal ("Stb" or "rE-
GEn")
max. 30 V DC
*)
0.01…2 A DC
25 Relay 1 / NC contact
RLB
26 Relay 1 / switching
contact
RLC
27 Relay 2 / NO contact
FLA
DC > 600V
Relay output
(DC > CP.19)
max. 30 V DC
*)
0.01…2 A DC
28 Relay 2 / NC contact
FLB
29 Relay 2 / switching
contact
FLC
*) The relay outputs must be operated with max. 48 V DC protective separation voltage to
guarantee the CE standard. After consultation with KEB, a current of max. 2 A AC is per-
missible for 120 V AC (depending on the switching capacity etc.).