Installation
4.
Installation
4.1
EMC-compatible control cabinet installation
1
Main fuse
150 mm
30 mm
150 mm
1
2
8
10b
9b
10a
10c
11
11a
12
4
3
5
150 mm
150 mm
6
7
9a
2
Main contactor
3
EMC side-mounted filter
(>=size 25 R-S or R6-N)
EMC sub-mounted filter
(<=size 19 R6-S)
4
If necessary, external voltage limi-
tation / synchronisation
5
Commutation reactor / harmonic
filter
6
COMBIVERT R6
7
if necessary, external DC fuses
8
Frequency inverter
9a
DC lines with ferrite
DC-
9b
Motor line with ferrite
10a Equipotential bonding with the
housing earth
10b Protective Earth (PE) on the
mounting plate power circuit
10c
Protective Earth (PE) on the
mounting plate control circuit
11
Mains connection power circuit
11 A Mains connection control circuit
12
Control lines
Large area contact at the mount-
ing plate
Figure 10:
EMC-compatible control cabinet installation
4.2
Installation instructions
Warning
General installation instructions
• Stationary install and earth COMBIVERT.
• The device must not be permeated by mist or water.
•
Allow for sufficient heat dissipation if installed in a dust-proof housing.
• Install the COMBIVERT in an appropriate housing in accordance with the local regulations
when operating it in explosion-endangered spaces.
• Protect COMBIVERT against conductive and aggressive gases and liquids.
• The lines of the R6-N commutation reactor must be limiting to 1m.
• The frequency inverter must be placed in the immediate environment of the R6-N.