19
Technical Data
Warning
General instructions
•
Voltage stabilization must be activated at the frequency inverter if a harmonic filter is used.
•
The units are not short-circuit proof without corresponding dimensioned fuses.
•
Exceeding of the max. rechargeable DC link capacity can lead to a defect.
•
A load removal in the DC link circle may be done only after the message „ready“.
•
If the control release is set when switching off the mains, this can lead to an overcurrent error and the
lifetime of the module can be reduced.
•
The unit must be disconnected from the supply system or the load must be switched off in case of overcur-
rent or overload.
3.3
Overload (OL) function
Standard:
105
110
120
130
140
150
160
100
150
200
250
270
60
Release time [s]
Load [%]
Figure 1:
Overload (OL) function
Modified standard (increased overload):
105 110
120
130
140
150
160
100
150
200
250
300
10
50
270
180
200
①
Release time [s}
Load [%]
1. Depending on the line supply impedance
Figure 2:
Overload (OL) function