Page 3.2 - 10
COMBIVERT R6-S
© KEB, 2008-02
Operating and appliance data
Parameter
Addr.
R PG E Min. value Max. value Res.
[?]
Default
ru.39 OL counter display
0227h ro
-
-
0
100
1
%
-
In order to prevent „E.OL“ - errors by overload (load reduction in due time), the internal count of the OL
counter can be made visible with this display. At 100% the COMBIVERT switches off with error „E.OL“. The
error can be reset only after a cooling time (blinking display „E.nOL“).
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.40
Power on counter
0228h rw
-
-
0
65535
1
h
-
The power on counter displays the time the inverter was switched on. The displayed value comprises all
operating phases. On reaching the maximum value (approx. 7.5 years) the indication remains on the maxi-
mum value.
Parameter
Addr.
R PG E Min. value Max. value Res.
[?]
Default
ru.41 Modulation on counter
0229h rw
-
-
0
65535
1
h
-
The modulation on counter displays the time the COMBIVERT was active (power modules controlled). On
reaching the maximum value (approx. 7.5 years) the indication remains on the maximum value.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.43
Timer 1 display
022Bh rw
-
-
0
655,35
0,01
-
-
The count of the free-programmable timer 1 is displayed. The display is done either in seconds, in hours
or in slopes/ 100 (see LE.21). The counter can be adjusted to any chosen value by keyboard or bus. The
programming of the counter is done with parameters LE.17...LE.21.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.44
Timer 2 display
022Ch rw
-
-
0
655,35
0,01
-
-
The count of the free-programmable timer 2 is displayed. The display is done either in seconds, in hours
or in slopes/100 (see LE.26). The counter can be adjusted to any chosen value by keyboard or bus. The
programming of the counter is done with parameters LE.22...LE.26.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.46
External temperature
022Eh ro
-
-
0
255
1
-
-
Overtemperature switch of the commutation throttle. Precondition for this function is a special power circuit.
The temperature detection is connected to the terminals T1/T2.
0:
T1/T2 closed
252:
power unit not ready
255:
T1/T2 open
Parameter
Addr.
R PG E Min. value Max. value Res. [?] Default
ru.68 Rated DC voltage
0244h ro
-
-
0
1000
1
V
-
This parameter displays the rated DC voltage automatically determined by the inverter. The value is measured
at switch-on.
Содержание combivert R6-S
Страница 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Страница 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Страница 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Страница 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Страница 40: ...Page 3 1 2 COMBIVERT R6 S KEB 2008 02 Parameter overview 3 1 1 Parameter list F5 A E and H 3 1 3 ...
Страница 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Страница 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Страница 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 146: ...Page 5 1 2 COMBIVERT R6 S KEB 2008 02 Error assistance 5 1 1 General 5 1 3 5 1 2 Error messages and their causes 5 1 3 ...
Страница 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Страница 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Страница 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Страница 166: ......
Страница 167: ......