Error assistance
Display COMBIVIS
Value Meaning
Error Messages
E.buS
Error ! Watchdog
18
Adjusted monitoring time (Watchdog) of communication between
operator and PC / operator and inverter has been exceeded.
E.EEP
Error ! EEPROM defective
21
After reset the operation is again possible (without storage in the
EEPROM)
E. EF
Error ! ERROR external fault
31
Is triggered, if a digital input is being programmed as external error
input and trips.
E.LSF
Error ! Load shunt fault
15
Error: Load-shunt relay has not picked up, occurs for a short
time during
the switch-on phase, but must automatically be reset immediately. If
the error message remains the following causes may be applicable:
- load-shunt defective
- input voltage wrong or too low
- high losses in the supply cable
E.nEt
Error! Mains
3
One or more phases are missing.
E.nOH
no E. over heat pow.mod.
36
No longer overheating in the interior E.OHI, interior temperature has
fallen by at least 5° C, error can be reset
E.nOHI no ERROR overheat int.
7
E.nOL
no ERROR overload
17
no overload, OL counter reaches 0 %; a cooling down phase must
be awaited after error E.OL. This message appears upon completion
of the cooling phase. The error can be reset now. The inverter must
remain switched on during the cooling phase.
E.OC
Error ! Overcurrent
4
Occurs, if the specified peak current is exceeded. Causes:
- acceleration ramps too short
- short-circuit at the output
- ground fault
- overload too high (e.g., deceleration ramp too high at the inverter)
- wrong parameterization
E.OH
Error ! Power module
temperature
8
Overtemperature of power module. Error can only be reset at E.nOH,
if the temperature has dropped by at least 5° C.
Causes:
-
insufficient air flow at the heat sink (soiled)
- ambient temperature too high
- ventilator clogged
E.OHI
Error ! Interior temperature
6
Overheating in the interior: error can only be reset at E.nOHI, if the
interior temperature has dropped by at least 5 °C.
E.OL
Error ! Overload (Ixt)
16
Overload, error can only be reset at E.nOL, if OL-counter reaches
0% again. Occurs, if an excessive load is applied longer than for the
permissible time (see technical
data). Causes:
- overload in the application
E.OP
Error ! Overvoltage
1
Voltage in the DC-link circuit too high. Occurs if the DC-link voltage
exceeds the permissible value. Causes:
- input voltage too high
- interference voltages at the input
E. Pu
Error ! Power unit
12
General power circuit error (e.g. switch-mode power supply or loading
shunt relay)
E.Puci
Error ! Power circuit unknown
49
During the initialization the power circuit could not be recognized or
was identified as invalid.
E.Puch Error ! Power unit code
changed
50
Power circuit identification was changed; with a valid power circuit this
error can be reset by writing to SY.03. If the value displayed in SY.03 is
written, only the power-circuit dependent parameters are reinitialized.
If any other value is written, then the default set is loaded. On some
systems after writing Sy.03 a Power-On-Reset is necessary.
further on next side
Содержание combivert R6-S
Страница 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Страница 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Страница 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Страница 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Страница 40: ...Page 3 1 2 COMBIVERT R6 S KEB 2008 02 Parameter overview 3 1 1 Parameter list F5 A E and H 3 1 3 ...
Страница 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Страница 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Страница 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 146: ...Page 5 1 2 COMBIVERT R6 S KEB 2008 02 Error assistance 5 1 1 General 5 1 3 5 1 2 Error messages and their causes 5 1 3 ...
Страница 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Страница 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Страница 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Страница 166: ......
Страница 167: ......