Error assistance
© KEB, 2008-02
COMBIVERT R6-S
Page 5.1 - 3
5
5. Error Assistance
The following chapter shall help you to avoid errors as well as help you to determine and remove the cause of
errors on your own.
5.1 Troubleshooting
5.1.1 General
If
error messages or malfunctions occur repeatedly during operation, the first thing to do is to pinpoint the exact
error. To do that go through the following checklist:
- Is the error reproducible?
For that reset the error and try to repeat it under the same conditions. If the error can be reproduced, the
next step is to find out during which operating phase the error occurs.
- Does the error occur during a certain operating phase (e.g. always during regeneration)?
If so, consult the error messages and remove the causes listed there.
- Does the error occur or disappear after a certain time?
That may be an indication for thermal causes. Check, whether the COMBIVERT is used in accordance to
the ambient conditions and that no moisture condensation takes place.
5.1.2 Error messages and their causes
At KEB COMBIVERT error messages are always represented with an „E.“ and the appropriate error in the
display. Error messages cause the immediate deactivation of the modulation. Restart possible only after reset
or autoreset.
Malfunction are represented with an "A." and the appropriate message. Reactions to malfunctions can vary.
Status messages have no addition. The status message shows the current operating status of the inverter (e.g.
forward constant run, standstill etc.).
In the following the display and their cause are described.
Display COMBIVIS
Value Meaning
Status Messages
nEtoF
Power-off
64
Mains power failure; regenerative operation is further possible, if the
disconnecting time E.nEt (Pn.14) > 0 s
nO_PU Power unit not ready
13
Power circuit not ready or not identified by the control.
noP
No operation
0
Control release (terminal ST) is not switched.
rEGEn
Regeneration active
66
Regeneration active (regenerative operation)
Stb
Standby
69
R6-S regenerative unit in stand-by operation (motor operation)
E.FnEt
Error! Mains frequency
40
Mains frequency outside the adjusted tolerance range (cS.03)
further on next side
Содержание combivert R6-S
Страница 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Страница 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Страница 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Страница 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Страница 40: ...Page 3 1 2 COMBIVERT R6 S KEB 2008 02 Parameter overview 3 1 1 Parameter list F5 A E and H 3 1 3 ...
Страница 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Страница 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Страница 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 146: ...Page 5 1 2 COMBIVERT R6 S KEB 2008 02 Error assistance 5 1 1 General 5 1 3 5 1 2 Error messages and their causes 5 1 3 ...
Страница 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Страница 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Страница 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Страница 166: ......
Страница 167: ......