63
DESCRIPTION Of THE TERMINALS
6.3.1.3 Temperature inputs
U
R1+
R1-
Terminals
Input type
X2A.10/12/14/16 R0+…R3+
Pt100
X2A.9/11/13/15
R0-…R3-
Connection
Measuring range
two-wire
-40…+80 °C
Figure 42: Temperature inputs
NOTICE
No potential separation !
The inputs are not electrically isolated from the control board, therefore
a motor temperature sensor must not be connected!
„5.7.3 Motor temperature detection“
6.3.1.4 Analog inputs
The analog inputs are optional.
AI0+, AI1+
AI0-,AI1-
I
Terminals
Differential inputs
X2A.6 / 8
AI0+/AI1+
AI 0, AI 1
X2A.5 / 7
AI0-/AI1-
Specification
Resolution
U/I
adjustable:
0…±10 V (Ri=55 kΩ)
0…±20 mA (Ri=250 Ω)
4…20 mA (Ri=250 Ω)
11 Bit + sign
Figure 43: Analog inputs
6.3.1.5 Relay output
RLA
RLC
Terminals
Output
X2A.1 / 2
RLA / RLC
Specification
U
dc
: Max. 30 V / 0.01…1 A
Max. number of switching cycles
10
8
mechanical; 500,000 at
U
dc
: 30 V / 1 A
Others
Ohmic load only, or inductive load with suitable protective
circuit
Figure 44: Relay output