38
Control circuit
4.3.7.2 Pin assignment encoder channel 2 (X3B)
SubD-9 connector (female)
5 4 3 2 1
9 8 7 6
Pin
Incremental encoder TTL
SSI
1
A+ Input channel A
CL+ Output clock signal
2
B+ Input channel B
DAT+ Input data channel
3
N+ Input zero track
–
4
5V Voltage output 5 V
5V
Voltage output 5 V
5
24V Voltage output 24 V
24V
Voltage output 24 V
6
A-
Differential signal to A+
CL-
Differential signal to CL+
7
B-
Differential signal to B+
DAT- Differential signal to DAT+
8
N-
Differential signal to N+
–
9
COM Reference potential
COM Reference potential
Housing GND Shielding of the encoder cable. Housing is connected internally to the
inverter earth (PE).
Figure 29: Pin assignment encoder channel 2 (X3B)
4.3.7.3 Encoder cable
General information on connecting encoder cables:
• Use encoder cable double shielded and twisted in pairs
• Connect outside shield to PE/GND at both ends. At the inverter end, connect outside
shield either
- onto the shield connection rail using shield connection clamps or
- to the housing of the SubD plug (connect inside the plug).
• •Connect interior shielding at one side at the inverter to COM
• do not connect outside and inside shield
GND
GND
A+, A-
B+, B-
N+, N-
COM
5/24V
Figure 30: Example for wiring an encoder cable