29
Power unit
4.2.4.2 Control of a 150…300 Vdc brake
Optional output to direct control of a brake with a rated voltage of 150…300 VDC (operating
voltage max. 420 Vdc; depending on dc link voltage).
Terminal strip X1B
Name
Description
HB+
HB-
U=150…300Vdc
HB+
max. 0.7 A; Free-wheeling diode is
internally available.
HB-
Functional earth
Figure 16: Connection of a high voltage brake
4.2.5 Connection of batteries/ultracapacitors
Terminal block X1B
Name
Description
BT+
BT-
BTM
+
+
+
+
F6
F7
BT+
DC input/output from 150 VDC for
the connection of ultracapacitors/
batteries for emergency operation.
Charging current control and moni-
toring is integrated in the unit.
BT-
BTM
Additional input for DC voltage
measurement against BT-.
Measuring range: 0…500 V
(Ri=500 kΩ)
Resolution: 10 Bit
(evaluation at PLC customer pro-
gram)
F6, F7
Fuses to protect energy storage
and wires recommended. They do
not serve to protect the COMBI-
VERT P6.
Functional earth
Figure 17: Connection of energy storages
Attention
no internal inrush current limiting
There is no internal inrush current limiting at the terminals BT+ and BT-. Therefore energy
storages supposed to connect only, if they are discharged. Instructions for switchgear use
at these terminals and for the recommended switching sequence on request at KEB.
Non-
observance may lead to damage the switching unit or at the terminals of the COMBIVERT P6.
4.2.6 Connection of an external braking resistor
The COMBIVERT P6 provides internal braking resistors as standard. If the COMBIVERT P6
included the option "for external braking resistor", the braking resistor must be connected
with shielded cable at RB+ und RB-. If the braking resistor isn't intrinsically safe, it must be
thermically monitored.