41
cONNecTION Of THe POWer UNIT
4.2.5 connection of a braking resistor
4.2.5.1 Terminal block X1B connection braking resistor
X1b
Name
function
cross-section
Tightening torque
++, R
Connection for
braking resistor
AWG
without
wire-end
ferrule
mm²
with
wire-end
ferrule
0.5…0.6 A
5…6 lb-inch
24...14
0.25...2.5
multi-wire
Figure 15: Terminal block X1B connection of a braking resistor
Terminal R can alternatively be labeled with PB.
4.2.5.2 Wiring of an intrinsically safe braking resistor
X1B
R
- -
++
U
V
W
①
②
Figure 16: Wiring of an intrinsically safe braking resistor
NOTICE
Only "intrinsically safe" braking resistors are permissible for this oper-
ation, since these resistors interrupt themselves at fault such as safety
fuse without fire risk.
Technical data and design for intrinsically safe braking re-
sistors.
www.keb.de/fileadmin/media/Manuals/dr/ma_dr_safe-braking-resis