45
cerTIfIcATION
• Wiring terminals are marked to show a range of values or a nominal value of tighten-
ing torque in pound-inches to be applied to the clamping screws as shown below:
Input/Output terminals: 5…7 lb-in (0.56…0.79 Nm)
• Use in a Pollution Degree 2 environment.
•
"Use 60/75°C Copper Conductors Only"
• “During the UL evaluation, only Risk of Electrical Shock and Risk of Fire aspects
were investigated. Functional Safety aspects were not evaluated”
• In order to comply with CSA C22.2 No. 14-2010 (cUL) following external Input
Chokes need to be installed: See table 1 below!
Table 1: Mains input chokes for cSA applications:
Cat. No. Housing Input Voltage [V]
Reactor Cat. No.
FLA Inductance [mH]
07G6
A
240 / 1ph
07DRF08-2951
10A
2.93
09G6
A
240 / 1ph
09DRF08-1851
16A
1.83
07G6
A
480 / 3ph
07DRB08-4951
3 x 6A
4.88
09G6
A
480 / 3ph
10DRB08-3751
3 x 8A
3.66
10G6
A
480 / 3ph
10DRB08-3751
3 x 8A
3.66
Branch Circuit Protection for G6 - A Drive series
I) Fuses:
Cat. No.
Housing
Input Voltage
[V]
Class CC, J or RK5
UL248 Fuse rating 600V [A]
07G6
A
240 / 1ph
15
09G6
A
240 / 1ph
20
07G6
A
480 / 3ph
6
09G6
A
480 / 3ph
10
10G6
A
480 / 3ph
10
The voltage rating of the external fuses shall be at least equal to the input voltage of the
drives.
WARNING – The opening of the branch circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or electrical shock,
current-carrying parts and other components of the controller should be examined and
replaced if damaged. If burnout of the current element of an overload relay occurs, the
complete overload relay must be replaced.
CSA: For Canada:
“ATTENTION - LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DU CIRCUIT
DE DÉRIVATION PEUT ÊTRE DÛ À UNE COUPURE QUI RÉSULTE D‘UN COURANT
DE DÉFAUT. POUR LIMITER LE RISQUE D‘INCENDIE OU DE CHOC ÉLECTRIQUE,
EXAMINER LES PIÈCES PORTEUSES DE COURANT ET LES AUTRES ÉLÉMENTS
DU CONTRÔLEUR ET LES REMPLACER S‘ILS SONT ENDOMMAGÉS. EN CAS DE
GRILLAGE DE L‘ÉLÉMENT TRAVERSÉ PAR LE COURANT DANS UN RELAIS DE
SURCHARGE, LE RELAIS TOUT ENTIER DOIT ÊTRE REMPLACÉ.”