WATer-cOOLeD DeVIceS
5.1.7 coolant heating with water
Volume flow depending on the total power dissipation and temperature difference be
-
tween forward flow and return flow.
0
1
2
3
4
5
6
7
8
9
10
4
5
6
7
8
9
10
①
②
③
3
2
1
④
Δ
T /
K
P
D_ges
1)
/ kW
Legend
Working area
①
5 l/min
②
10 l/min
③
12.5 l/min
④
15 l/min
Figure 33: Volume flow depending on the total power dissipation PD_ges and temperature difference with
water-glycol mixture
1)
P
D_ges
can be higher than the power dissipation P
D
at rated operation due to overload, higher switching
frequency or sub-mounted braking resistores.
The minimum volume flow depends on the power dissipation.