cONNecTION OF THe POWer UNIT
4.2.1.1 Terminal block X1A for 400 V units
Name
Function
Terminal connec-
tion
Tightening
torque
crimp con-
nector dimen-
sion type
Max. num-
ber of con-
ductors
1)
L1
Mains connection
3-phase
8 mm stud for
M8 crimp connec-
tor
10...15 Nm
88...132 lb inch
1
For IEC: 2
For UL: 2
L2
L3
+
DC terminals
2
-
R
Connection for braking re-
sistor (b and R)
U
Motor connection
1
V
W
Figure 20: Terminal block X1A for 400 V devices
1)
From 50mm² only one conductor allowed
crimp connector dimension
Type 1
Type 2
Max. width
l / mm
24
19
Max. shaft length
l / mm
46
46
Max. diameter
l / mm
19
19
Table 30:
Crimp connector dimension X1A
Alternatively to a 95 mm² line, 2 parallel 35 mm² lines can also be laid.
NOTICE
Short circuit due too low air and creepage distances!
►
The pressing of the crimp connectors must point upwards when
connecting 95 mm² lines!