GeNerAL eLecTrIcAL DATA
Device size
21
22
23
24
Rated DC link voltage @
U
N
=
400V
U
N_dc
/ V
565
Rated DC link voltage @
U
N_UL
=
480V
U
N_dc_UL
/ V
680
DC link voltage working voltage range
U
IN_dc
/ V
390...780
DC switch-off level "ERROR underpotential“
U
UP
/ V
240
DC switch-off level "ERROR overpotential“
U
OP
/ V
840
DC switch-off level braking transistor
1)
U
B
/ V
780
Max. braking current
I
B_max
/ A
168
Min. braking resistor value
R
B_min
/ Ω
5
Braking transistor
2)
Max. cycle time: 120 s; ED: 50 %
Protection function for braking transistor
Short-circuit monitoring
Protection function braking transistor
(Error GTR7 always on)
3)
Feedback signal evaluation and
current shutdown
DC link capacity
C
/ µF
3300
3900
5200
6200
Table 24:
DC link / braking transistor function of the 400 V devices
1)
The DC switching level for the braking transistor is adjustable. The default value is the value specified in the
table.
2)
The ON time is additionally limited by the used braking resistor
3)
The feedback signal evaluation monitors the functionality of the braking transistor. The current is switched
off via the internal mains input bridge of the AC supply.
3.3.3 Sub-mounted braking resistors
Technical data of the sub-mounted braking resistors
Braking resistor value
R
/ Ω
8
Rated power
P
D
/ W
730
Cyclic duration factor referring to
120s @
U
_dc
= 780V
ED
/ s
0.9
Table 25:
Sub-mounted braking resistors
NOTICE
Observe the power dissipation of the sub-mounted braking resis-
tors
In braking mode with sub-mounted braking resistors, the power to be
dissipated of the heat sink will be increased.
►
Consider the power dissipation of the braking resistors when de-