3.3 General electrical data
3.3.1 Switching frequency and temperature
The drive controller cooling is designed by way that the heat sink overtemperature
threshold is not exceeded at rated conditions. A switching frequency higher than the rat-
ed switching frequency also produces higher losses and thus a higher heat sink heating.
If the heat sink temperature reaches a critical threshold (
T
DR
), the switching frequency
can be reduced automatically step by step. This prevents that the drive controller switch-
es off due to overheating of the heat sink. If the heat sink temperature falls below
T
UR
,
the switching frequency is increased back to the setpoint. At temperature
T
EM
the switch-
ing frequency is immediately reduced to rated switching frequency. "Derating“ must be
activated, for this function to work.
Device size
21
22
23
24
Rated switching frequency
1)
f
SN
/ kHz
8
4
2
4
8
2
4
Max. switching frequency
1)
f
S_max
/ kHz
16
Min. switching frequency
1)
f
S_min
/ kHz
1.25
Max. heat sink temperature
T
HS
/ °C
90
90
95
67
95
87
Temperature for derating the switching
frequency
T
DR
/ °C
84
84
85
57
85
77
Temperature for uprating the switching
frequency
T
UR
/ °C
70
70
75
50
75
67
Temperature for switching to rated switching
frequency
T
EM
/ °C
87
87
90
62
90
82
Table 23:
Switching frequency and temperature of the 400 V devices
1)
The output frequency should be limited in such a way that it does not exceed 1/10 of the switching frequen-
cy.