Page 7.1 - 22
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Operating and appliance data
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
Sy.11
Baudrate int. Bus
000Bh RW
-
+
3
11
1
-
11
The transmission rate between operator/inverter or PC/inverter is determined with the internal baudrate.
Following values are possible:
Value
Baud rate
Value
Baud rate
Value
Baud rate
3
9.6 kBaud
6
55.5 kBaud
9
115.2 kBaud
4
19.2 kBaud
7
57.6 kBaud
10
125 kBaud
5
38.4 kBaud
8
100 kBaud
11
250 kBaud
After Power-On it is always started with 38.4 kBaud and dependent on the operator higher set.
Parameter
Addr.
R
PG
E
Min. value
Max.
value
Res.
[?]
Default
Sy.17
Proc. read data 1 set
0011h
*
-
+
1
128
1
hex
1
SY.19
Proc. read data 2 set
0013h
*
-
+
1
128
1
hex
1
SY.21
Proc. read data 3 set
0015h
*
-
+
1
128
1
hex
1
Sy.17
Proc. read data 4 set
0016h
*
-
+
1
128
1
hex
1
* rw via bus; r via keyboard
Parameter
Addr.
R
PG
E
Min. value
Max.
value
Res.
[?]
Default
SY.16
Proc. read data 1 defi
-
nition
0010h
*
-
+
-1
7FFFh
1
hex
-1
SY.18
Proc. read data 2 defi
-
nition
0012h
*
-
+
-1
7FFFh
1
hex
-1
SY.20
Proc. read data 3 defi
-
nition
0014h
*
-
+
-1
7FFFh
1
hex
-1
SY.22
Proc. read data 4 defi
-
nition
0016h
*
-
+
-1
7FFFh
1
hex
-1
* rw via bus; r via keyboard
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
SY.32
Scope timer
0020h
RO
-
-
0
65535
1
-
0
The scope timer generates a time period of 1 ms. This can be used by external programs, e.g. scope, to re-
present time patterns. The timer counts from 0...65535 and starts again with 0 after an overflow.
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
SY.41
Control word high
0029h
RW
-
+
0
65535
1
-
0
The control word is used for state control of the inverter via bus. The control word long (Sy.43) consists of the
two 16 bit parameters control word high (Sy.41) and control word low (Sy.50). The status word is bit-coded.
The description of the individual bits is found in chapter 10.1.
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
SY.42
Status word high
002Ah
RO
-
-
0
65535
1
-
0
With the status word the current condition of the inverter can be readout via bus. The status word long (Sy.44)
consists of the two 16 bit parameters status word high (Sy.42) and status word low (Sy.51). The status word
is bit-coded. The description of the individual bits is found in chapter 10.1.
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...