Protective functions
Pn.60: Quick stop time
Value
Explanation
0...300 s
Deceleration ramp for abnormal stopping-function
At abnormal stopping with differential controller
, this ramp is modified that the drive decelerates preferably at a
current limit.
This current limit is set in Pn.59 "abnormal stopping level".
Pn.59: Quick stop level
Value
Explanation
0...200%
Current limit for deceleration = 0..200% rated inverter current (In.01)
With Pn.58 bit 1 can be selected if the inverter shall decelerate at the active current limit or at the apparent
current limit.
Scheinstrom (ru.15)
Umrichternennstrom (In.01)
Wirkstrom (ru.17)
Umrichternennstrom (In.01)
Schnellhalt Pegel (Pn.59)
-
1
Schnellhalt Rampenzeit (Pn.60)
Schnellhalt Modus (Pn.58)
Bit 0
0
1
+
+
aktuelle Rampenzeit
Time monitoring abnormal stopping
For safety, a maximum time for the abnormal stopping-function can be programmed.
Pn.68: Max. abn. stopping time
Value
Explanation
0,01...100,00 s
time after which the inverter switches from malfunction- ("abnormal stop" A.XX) to the error
state (E.XX)
If the inverter is still in the malfunction state (A.XX) after this time (no RESET or automatic restart was exe-
cuted), the inverter switches off the modulation and changes to the corresponding error state (A.XX => E.XX).
Abnormal stopping via control word
Abnormal stopping can also be triggered via the control word (SY.43 and SY.50, respectively ). The parameter
Pn.58 abnormal stopping mode determines the behaviour of the abnormal stopping via control word.
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...