Page 7.5 - 22
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Motor data and controller adjustments of the asynchronous motor
7.5.2.3.3
Generally adjustments for operation with motor model
The drive is only ready for operation after switching the modulation if the flux is build up. If one starts earlier,
the drive can
display undefined behaviours (erroneous torque
display, too high currents, poorer controller be-
haviour).
dS.04 : Flux / rotor adaption mode
Bit
Meaning
Value
Explanation
7
Wait for magnetisati-
on (ASM)
0: off
128: on
The speed setpoint (
ru.01) is applied only after the flux build-up, i.e.,
only then ramps and speed controller become active
Bit 7 in dS.04 ("Wait for magnetisation (ASM)") must therefore always be set (value 128). Thus the setpoint
setting is only released if the flux is build up to 95%.
0%
20%
40%
60%
80%
100%
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
Zeit [s]
Sollwertanzeige (ru.01)
Anzeige Rampenausgang (ru.02)
Reglerfreigabe (ST)
Fluss / Nennfluss
The flux controller must be
activated for the operation with motor model.
The parametrisation of
the controller (KP flux / dS.11, KI flux / dS.12, limit magnetising
current / dS.13) is carried
out automatically by Fr.10 and after the motor identification (dr.48).
dS.04 Flux/rotor adaption mode
Bit
Meaning
Value
Explanation
5, 6
Flux control
(ASM)
0: off
Flux controller always off (these adjustment is not allowed for the ope-
ration with motor model)
32: on
flux controller always on (must be used for control with motor model
and encoder feedback)
64: on,
n^3/dr.17^3
flux controller active, speed-dependent limit of the controller (at speed
0 = 0 / at speeddr.17 = dS.13)
96: on,
start and
n^3/dr.17^3
as value 64, exception: start of the drive:
here, (despite speed 0) for magnetisation the limit of the flux controller
is set to the value dS.13.
During operation with speed feedback, the flux
controller must be activated over the whole speed range, i.e.,
the value 32 must be chosen in dS.04 in the item "
flux control".
Value 64 or 96 should be selected during operation without speed feedback.
With Fr.10, the parameter dS.13 "Limit magnetising current" is set to half the rated motor current
. If the flux
build-up
time is to be shortened or if particularly high demands are made on the dynamics in the field weakening
range, this value can be changed to the rated motor current (dr.00).
The inverter can only provide the standstill current at speed 0. Error OL2 is released shortly if the current is
Содержание COMBIVERT F5-A
Страница 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Страница 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Страница 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Страница 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Страница 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Страница 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Страница 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Страница 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Страница 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Страница 200: ...Page 7 5 38 COMBIVERT F5 A E H KEB 2012 10 Motor data and controller adjustments of the asynchronous motor...
Страница 207: ...Motor data and controller adjustments of the synchronous motor KEB 2012 10 COMBIVERT F5 A E H Page 7 6 7 7...
Страница 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Страница 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Страница 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Страница 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Страница 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Страница 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Страница 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Страница 480: ...Page 8 1 2 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting 8 1 1 General 8 1 3 8 1 2 Error Messages and their Cause 8 1 3...
Страница 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Страница 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Страница 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Страница 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...