11.2.4 DRIVECOM
DRIVECOM e.V. is a user group of leading manufacturer in the power transmission.
Based on InterBus a uniform communication profile was defined. The following
profile parameters are an extraction from it and are limited to the parameters
necessary for inverter operation. The description of the entire communication profile
is found in the DRIVECOM specifications.
The DRIVECOM profile offers the possibility to address units from different
manufacturer via a unitform control profile. The units are then put into the various
operating states by means of the DRIVECOM control word (Pr.6).
With parameter ud.5 the operation via the DRIVECOM control word is activated or
deactivated. Furthermore, it is defined how the parameter value is adjusted. When
determining the pole number from the motor data the value is programmable in the
sets 0...7. The control word itself is a part of the profile parameters.
ud. 5
Control word
Value adjustment
Pole number
0
Off
oP-Parameter
Pr. 4
1
On
oP-Parameter
Pr. 4
2
Off
Profile parameter
Pr. 4
3
On
Profile parameter
Pr. 4
4
Off
oP-Parameter
Motor data
5
On
oP-Parameter
Motor data
6
Off
Profile parameter
Motor data
7
On
Profile parameter
Motor data
11.2.6 Profile Parameters
Pr. 4 Pole number
012Ah
2
12
2
4
-
Adjusts the pole number of the connected motor. Adjusted is a 4-pole motor.
Pr. 5 Error code
0105h
0
65535
1
-
-
Gives out the error code in case of malfunction. The code is described in 6.1.4 „ru. 0“.
Pr. 6 Control word
0106h
0
65535
1
0
-
The control word serves for the state control of the inverter by bus. In order for the inverter to respond to the
control word it must be activated with parameter ud.5.
11.2.5 Activating Profile
Parameters
Pr (PROFILE)-PARAMETER correspond to the DRIVECOM specification. They
are intended exclusively for bus operation and are not visible on the display. Profile