33
INSTALLATION AND CONNECTION
4.6 Control cabinet installation
NOTICE
Observe installation position!
The sine-wave filters must always be mounted hanging with the venti
-
lation grilles downwards and the cable versions upwards in the control
cabinet. In case of another installation method, please contact KEB.
4.6.1
Installation distances of the sine-wave EMC filters
Installation distances
Dimen-
sion
Distance in mm
Distance in inch
A
B
D
E
F
C
D
A
150
6
B
100
4
C
0
0
D
0
0
F
1)
20
1
1)
Distance to upstream operating elements in the
control cabinet door.
Figure 17:
Installation distances of the sine-wave EMC filters
4.6.1.1 Mounting instructions for control cabinet installation
For mounting the sine-wave EMC filters, the following mounting materials with the ap
-
propriate quality must be used.
Filter type 0D, 0H and 0L
Tightening torque
Socket screw with hexagon socket
- M8 - 8.8
6.0 Nm
53 lb inch
Filter type 0P, 0S, 0X and 0y
Tightening torque
Socket screw with hexagon socket
- M10 - 8.8
10.0 Nm
88.5 lb inch