Programming

  Press & hold ENTER button 

to access setpoint menu

  Use arrow buttons to 

select function:

tS    =  Temperature Setpoint

diF   =  

CSH  =  Max Compressor 

Starts/ Hour

dPd  =  Defrost Per Day

dFt  =  Defrost Time

LAO =  

tAd  =  Temp Alarm Delay

Adr  =  Mod Bus Address

Unt  =  Units for temp display

  Press ENTER & use arrows 

to change value

  Press & hold ENTER button 

Alarms

  When amber LED is lit:

SSA  =  Shorted Sensor Alarm

OSA  =  Open Sensor Alarm

HtA  =  High Temp Alarm

LtA  =  Low Temp Alarm

pn 20679  

 06/14

© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.3.20 (Q.1.20)

October 2016

KE2 Temp 

+ Defrost 

(pn 20611)

For 

Medium Temperature

 Applications with 

Air Defrost

Installation Manual

Supplies List

All of the accessories required for the controller to work 

are supplied, however, standard truck stock items are re-

quired to install the controller.  A list is provided below:

  conduit to go between the controller & evaporator

  (2) conduit connectors (straight or elbow as required)
  (4) high voltage wires matched to the load of the 

liquid line solenoid/compressor and the controller.

  wire labeling (numbers, colors, etc.)
 additional wire ties
 18 gauge twisted shielded pair
 (if extending sensor 

wires/adding communication)

 foam insulation (if running wires outside the space)
 silicone (for sealing any box penetrations)

This reference should remain on site with the installed KE2 Temp + Defrost controller.

What’s in the Kit - Parts List

The following parts are included in the 

KE2  Temp + Defrost kit:

  (1) KE2 Temp + Defrost controller
  (1) temperature sensor - 45”
  (4) self-tapping mounting screws
  (1) liquid tight cord grip 
  (1) sensor ziptie
  (1) programming sticker
  (2) screws for high voltage shield

B

C

D

E

F

Select Mounting Location

The KE2 Temp is designed for a wide range of applications; therefore 

there are many potential installation locations. Breaking down the in-

stallation location by application provides the most helpful reference.

Application

Locations

Under counter

Evaporator cabinet

Outside controlled space

Walk-in

Evaporator cabinet

Adjacent to entrance

Side-by-side

Above door

Walk-in

Under Counter

Commercial

Wine Cabinet

A

F

A

C

D

E

B

F

G

Quick & Easy

Remote Communication, 

Control & Alarming 

when used with 

the KE2 LDA

Remote Monitoring, Control, Alarm Notifications

The KE2 Temp includes RS-485 Modbus communications, and can now 

be accessed remotely using the KE2 Local Area Dashboard and Alarms 

(KE2 LDA). See page 4 for additional details.

Service Call Saver -

 

Post Defrost Indicator

To eliminate unnecessary service calls, the KE2 Temp + Defrost alerts 

the user when it is coming out of a defrost cycle using the onboard 

display. The display alternates between dEF and the actual temperature 

measured by the air sensor.  This continues until the temperature has 

reached setpoint, or for the amount of time set by dFt (Defrost Time) 

whichever is shorter.

Содержание KE2 Temp + Defrost

Страница 1: ...site with the installed KE2 Temp Defrost controller What s in the Kit Parts List The following parts are included in the KE2 Temp Defrost kit 1 KE2 Temp Defrost controller 1 temperature sensor 45 4 s...

Страница 2: ...40V to power the controller and 12V 240V sole noid voltage via the liquid line solenoid relay through the lower con duit connection The temperature sensor and communication wires are attached via the...

Страница 3: ...ted to the NO normally open terminal the left most terminal location Proper wiring practices must be followed Local wiring codes take precedence over any information in this bulletin 6 VoltageTable Ou...

Страница 4: ...uring holidays or vacations Just go online and see or setup the email text alarm alerts feature for instant notification of system issues More information on KE2 Smart Access is found in bulle tin Q 1...

Страница 5: ...tpoint ENTER Press to move between the digits to accelerate the changes ENTER Press and hold to confirm each setpoint change BACK Press to escape Only visible if CUS custom is selected for dPd Defrost...

Страница 6: ...rost 12 00 dis disabled 23 dis disabled d11 Start time of Defrost 11 00 dis 23 dis d10 Start time of Defrost 10 00 dis 23 dis d9 Start time of Defrost 9 00 dis 23 dis d8 Start time of Defrost 8 00 dis...

Страница 7: ...to the nearest 10 minutes See exam ples below Examples then press Use the up arrow and down arrow to set the time STEP 7 Press the button to save set tings and return to the main screen room temp wil...

Страница 8: ...olutions 12 Chamber Drive Washington MO 63090 1 888 337 3358 www ke2therm com Q 3 20 Q 1 20 October 2016 Page 8 KE2 Temp Defrost pn 20611 For Medium Temperature Applications with Air Defrost Installat...

Отзывы: