54 - EN
PAR
DESCRIPTION
DEFAULT
min
MAX
REGULATION
R01
Hysteresis for compressor and resistance activation
2°C
0°C
20°C
R02
Minimum time between 2 successive compressor switch-ons
0 min
0 min
30 min
R03
Compressor activation delay from board activation
30 sec
0 sec
300 sec
R04
Minimum time between compressor switch-on/off
60 sec
0 sec
300 sec
R07
Maximum daily limit of compressor use
100 %
0 %
100 %
R08
Number of thermostating cycle in the Cycle Test
3
0
10
R09
Maximum SetPoint value accepted
50°C
-50°C
50°C
R10
Minimum SetPoint value accepted
-5°C
-50°C
50°C
R11
Minimum time between compressor switch-off/on
60 sec
0 sec
300 sec
R12
Cycle Test start temperature
18°C
-50°C
50°C
R13
Humidity hysteresis
5 %
0 %
15 %
R14
Steam injection duration
20 sec
0 sec
60 sec
R15
Humidity cycle duration
1 min
0 min
300 min
FANS
F01
Enable evaporator fans
(0 disabled; 1 Enabled)
1
0
1
F03
Evaporator fans set
50°C
-50°C
50°C
F05
Evaporator fans in defrost
(0: OFF 1:ON)
0
0
1
F07
Evaporator fan activation delay from defrost end
180 sec
0 sec
300 sec
F13
Extractor fan activation interval
0: only manual activation/deactivation
1 h
0 h
120 h
DEFROST TIME
H01
First defrosting time (24 h = excluded)
1 h
0 h
24 h
H02
Second defrosting time (24 h = excluded)
24 h
0 h
24 h
H03
Third defrosting time (24 h = excluded)
24 h
0 h
24 h
H04
Fourth defrosting time (24 h = excluded)
24 h
0 h
24 h
PR1
Sampling time
30 min
1 min
300 min
PR2
Type of daily printing:
0: None;
1: Alarms;
2: Alarms and cell probe;
3: Alarms and all probes;
3
0
3
COMMUNICATION
ADD
Instrument address
1
1
247
SC
Serial Management:
0: Not used
1: Print
2: ModBus
2
0
2
MB1
BaudRate:
0 = 2400;
1 = 4800;
2 = 9600;
2
0
2
MB2
Parity : 0 = no parity; 1 = odd; 2 = even
2
0
2
NMP
Parameters map number
0
0
1000
E01
Humidity probe calibration
0 %
-20 %
20 %