EDEBD

A0224-3823-1_EN

User manual

Technical parameters

Your partner for 

network analysis

multimess D6

System 

I

 English

Содержание multimess D6

Страница 1: ...EDEBDA0224 3823 1_EN User manual Technical parameters Your partner for network analysis multimess D6 System I English...

Страница 2: ...safety relevant symbols 5 1 4 Safety notes 6 1 5 Product liability 7 1 6 Disposal 7 2 Device memory 8 3 Definition of terms 9 4 Field of application range of functions 10 5 Connecting the multimess D6...

Страница 3: ...ry and operation logbook 36 8 4 3 Measurement period synchronization 37 8 4 3 1 Synchronization only by internal clock 37 8 4 3 2 Synchronization by the KBR eBus 38 9 Serial interface 38 9 1 Operating...

Страница 4: ...in the switchgear cabinet Even if the de vice is resold to third parties the manual remains an inherent part of the device Although the utmost of care has been taken in putting together this user man...

Страница 5: ...n Caution Caution means that minor injuries or damage may occur if suitable safety precautions are not taken Note Note is an important piece of information on the product its operation or the respecti...

Страница 6: ...ice name plate Caution A faulty connection may result in the destruction of the device For device connection the data given in the connection chart must be com plied with see Connection chart and ther...

Страница 7: ...um reliability are used Each device is subject to long term testing before it is delivered For details on product liability please refer to our general terms and conditions for electronic equipment wh...

Страница 8: ...ck RTC After an uninterrupted charging time device connected to the supply voltage of approx 8 hours the buffer capacitor will have a sufficient charge to protect the internal clock from failure due t...

Страница 9: ...ting scanning spots are available for further calculations This interval is mainly determined by the A D conversion Measuring cycle The measuring cycle is the time the measuring device needs in order...

Страница 10: ...e status and monitor the functions Four buttons facilitate clearly structured navigation through the menus For 100 to 400 V networks The multimess D6 can be applied in three wire as well as four wire...

Страница 11: ...In addition to its counting functions the multimess D6 offers extensive memo ry functions 4 quadrant load profile memory to record the cumulated active and reactive power Memory to record the daily en...

Страница 12: ...only be connected on one side During installation please also observe our notes on safety measures against overvoltage and lightning in the chapter Protective measures of this manual Note You should...

Страница 13: ...Tarif Tariff Schnittstelle Interface Modbus Connecting the multimess D6 Assigning measuring voltage input current transformer input The current transformer on terminal 20 21 k1 l1 must be arranged in...

Страница 14: ...g inputs Three phase voltage measurement in 4 wire alternating current networks Direct measurement is possible in the following networks 3 x 100V 57 7V AC 3 x 400V 230V AC For higher voltages the unit...

Страница 15: ...different messages 6 2 LEDs LED K While the LCD shows the type of measurement and the measured LED M numerical value the three prefix LEDs K M and G show the LED G significance of the unscaled unit I...

Страница 16: ...ing Start time 00 00 for LT start End time 00 00 for LT end All measurements Restart Energy Memory Deleting all energy memories Measurement period 15 min Measurement period memory Deleting all entries...

Страница 17: ...s Tariff switching user can select digital input switching via KBR eBus or at times programmed in the device Synchronization settings Setting options Bus and internal clock Bus mode Choice of KBR eBus...

Страница 18: ...ir representation on the device The respective measuring range is automatically switched over in the display T1 12 Wh G M k T1 345 Wh G M k T1 678 9 Wh G M k Example Display 7 1 Display of active or r...

Страница 19: ...measured values themselves the same principles apply as for the display of active and reactive energy The output measuring value must be multiplied with the respective display significance Kilo Mega o...

Страница 20: ...mulated active energy in low tariff The tariff display T2 low tariff lights up permanently The tariff display T1 flashes i e the current counting tariff is T1 high tariff T1 2 35 Wh T2 Menu LCD Unscal...

Страница 21: ...e available Continue in the main menu or For meter count detailed view 2 Wh T2 Detailed view gigawatt hours GWh if the prefix LED G is active Continue with or to jump back to the basic menu 456 Wh T2...

Страница 22: ...if the prefix LED M is active Continue with or to jump back to the basic menu T1 789 5 Varh Detailed view kilovar hours kvarh if the prefix LED K lights up Back to main menu or Reactive energy WReact...

Страница 23: ...LED K lights up Back to main menu or Voltage Ph N L1 uI 230 V V if no prefix LED is active Continue with to L2 and L3 or to the basic menu Voltage Ph Ph L1 2 uI P 398 V V if no prefix LED is active Co...

Страница 24: ...refix LED is active Power factor PF 0 52 Display of the power factor funda mental component and harmonics Device time 12 34 55 Output format Hours Minutes Seconds Devices date 12 04 15 Output format D...

Страница 25: ...to next item Changes to the input mode i e the first place of the value to be modified flashes Pressing the key again will jump to the second place of the value to be modified etc Pressing the key st...

Страница 26: ...ription Reset rESEt Reset should only be carried out during setup and when the device is completely reprogrammed Caution Reset will reset all programmed values back to default settings Jump to the nex...

Страница 27: ...s been performed resetting the device to factory defaults Enter password Cd0000 Password is queried only when password 9999 is not used Password 9999 in original state or after reset access to all inp...

Страница 28: ...g you can add a decimal point with the button The prefix LED K will then also light up next to the display Menu Key combination Device display Description Measuring voltage secondary U5 400 V e g Oper...

Страница 29: ...ory T1 CLEAr Wh T2 Varh Menu to delete all energy memories Note Delete functions can only be carried out after the appropriate password has been entered Procedure for delete functions Press both keys...

Страница 30: ...n deleted Pulse output proportional to active or reactive energy on consumption or recovery PULS P W Pulse output type kWh in prop to active or reactive energy W in prop to active energy Var in prop t...

Страница 31: ...od t2 d16 Switching T1 T2 by floating contact save with t2 d16 Change switching meth od switching possibilities as follows diG signal on digital input buS via Energy Bus command or Int internally prog...

Страница 32: ...nter nal synchronization or SY buS synchroniza tion through energy bus command and internal clock save with 5Y bUS Bus mode Ebus KBR eBus active Change Bus mode The following switching possibilities s...

Страница 33: ...s assigned automatically by the PC software and the address is entered in the device memory Ad 0001 With the key the automated process can be stopped and an address can be entered manually Jump to the...

Страница 34: ...od is finished at the next synchronization event and saved If the time of the multimess D6 is moved back by more than the duration of one period the load profile memory is deleted and restarted In bot...

Страница 35: ...The period duration can be set by the user via PC software to 60 30 15 or 1 minute the number of entries is 3840 This means that a period duration of 60 minutes results in a maximum storage duration o...

Страница 36: ...a ring buffer The following events and entries are recorded Events Recording Event memory Event memory deleted Tariff input Switchover signal HT LT with date and time Switchover signal LT HT with date...

Страница 37: ...ss changed old address new address Controlled restart Reboot Firmware Firmware updated Watchdog Restart Watchdog Note The described memories can only be read out via the KBR eBus by means of optionall...

Страница 38: ...isys D2 ESES bus repeater Using the relevant Windows software all bus devices can be configured and visualized We will be glad to provide information on which other devices you can connect to the Ener...

Страница 39: ...the error message is displayed The error message e rnge is displayed Check the connected measuring voltage and the voltage transformer This message appears if the rated voltage of 400 V is exceeded by...

Страница 40: ...red Reset the device Note Take notes of all programmed parameters as they will return to their default settings after the reset After resetting the multimess D6 must be programmed again The error mess...

Страница 41: ...prefix LED G is active Display range 0 0000 kVArh to 9999 GVArh auto range switching Active power Calculation P PL1 PL2 PL3 display of phase power only via Energy Bus Units W if no prefix LED is acti...

Страница 42: ...ins the first and overharmonics Display range 0 00 p1 00 Voltage RMS value of a measurement interval Phase N UL1 N UL2 N UL3 N Phase Phase UL1 L2 UL2 L3 UL3 L1 Units V if no prefix LED is active KV if...

Страница 43: ...requency correction between 45 65 Hz 11 4 Device memory Data storage 1 MB flash non volatile Memory type Ring buffer Long term memory 1 year Annual energy memory Daily values for active and reactive e...

Страница 44: ...20 V AC measuring range 1 3 30 V 400 V 480 V AC measuring range 2 Input imped ance 1 8 MOHM Ph Ph Measuring range programmable Current measuring inputs IL1 IL2 IL3 3 0 01 A 1 A 1 2 A AC measuring rang...

Страница 45: ...ulse length default 100 ms 30 990 ms configurable on the device Interpulse period Pulse length External voltage supply max 35V 30 mA DC ensure correct polarity Serial inter face BUS RS485 for connecti...

Страница 46: ...protection F1 Recommendation 1 AT fuse 4 AT BUS Connection Connection material For proper operation please only use shielded twist ed pair cables e g I Y St Y EIB 2x2x0 8 Pulse output Connection and c...

Страница 47: ...p hat rail device Housing dimensions 90 x 106 4 x 61 mm H x W x D Mounting type Wall mounting on DIN rail 7 5 mm deep in accor dance with DIN EN 50022 suitable for distribution board mounting Weight A...

Страница 48: ...o 55 C Humidity 5 to 95 non condensing Storage tem perature 25 C to 70 C Operating altitude 0 to 2000 m above sea level Electrical safety Standards DIN EN 61010 1 2011 07 DIN EN 61010 2 030 2011 07 Pr...