A0193_1112-1_GB
multimess
System
I
English
User manual
Technical parameters
1D4
Your partner for
network analysis
Energy measuring device
Страница 1: ...EDEBDA0193_1112 1_GB multimess System I English User manual Technical parameters 1D4 Your partner for network analysis Energy measuring device ...
Страница 2: ... KBR Kompensationsanlagenbau GmbH Subject to technical changes 2 ...
Страница 3: ...sembly 14 Connections 15 Start up 16 Start up of the multimess 1D4 with multimess 1F96 DS display 16 Start up of the multimess 1D4 at the multisio 6D6 with multisio 6F96 DS 19 Start up of the multimess 1D4 with multisys 3D2 ESBS 20 System operation 20 Configuration of system parameters in the Extras menu 20 Commi function 22 Para function 22 Consumption monitoring 22 Menu overview 24 Technical dat...
Страница 4: ... and miscellaneous 31 Technical data of the measuring module 32 Power supply 32 Hardware inputs and outputs 32 Electrical connection 32 Mechanical data 32 Standards and miscellaneous 33 Protective measures 33 Overvoltage and lightning protection 33 Index 34 ...
Страница 5: ...ion with multimess 1F96 DS display For other device versions e g for multimess 1D4 on multisio 6D6 with multisio 6F96 DS or multimess 1D4 with multisys 3D2 ESBS please read the respective device manual This user manual is included in the scope of delivery of the device and must be accessible for the user at all times e g in the switchgear cabinet Even when the device is resold to third parties the...
Страница 6: ...ns that minor injuries or damage may occur in case the appropriate safety measures are not taken Note is an important information on the product its operation or the respective part of the user manual to which special reference is made Disclaimer The content of this user manual has been carefully reviewed in terms of the hardware and software described Certain deviations however cannot be excluded...
Страница 7: ...y conditions comply with the specifications on the nameplate A faulty connection can lead to the destruction of the device When connecting the device observe the connection chart see chapter Connection chart and make sure that no voltage is applied to the connection lines Only use proper wiring material and observe the correct polarity when wiring In order to ensure proper and safe operation of th...
Страница 8: ... components of the highest reliability and quality were used Each device is subject to long term testing before it is delivered Regarding product liability we refer to our general terms and conditions for electronic equipment which you can find at www kbr de The warranted characteristics of the device only apply for operation in accordance with its intended use 1 6 Disposal Defective outdated or n...
Страница 9: ...mess 1D4 BS with multimess 1F96 DS Connection of the optional multimess 1F96 DS display can be established with a ready made RJ12 cable For operation of the display an additional power supply unit is needed e g the multisys 1D4 PS 24V This way no complicated wiring of voltage and current paths from the converter to the switchgear cabinet door is necessary Up to 10 measuring modules can be read out...
Страница 10: ...dule bus interface via ready made RJ12 cables A maximum of 15 measuring modules can be connected power consumption of the measuring module interface approx 0 3 W power output of the multisys 3D2 ESBS gateway approx 5 W at 24 VDC For a larger number of measuring modules the multisys 1D4 PS 24V power supply unit is required power output 24 VDC 10 W 3 Device overview multimess 1D4 measuring module Fo...
Страница 11: ...peration via sensor buttons Mounting depth 40 mm Door assembly cut out 92x92 mm Module bus connection RJ12 for measuring modules and supply voltage Display of momentary current and voltage values Continuous energy meter for active and reactive energy Management of up to 10 measuring modules Assignment of station names to the measuring modules Display language selectable German deut English engl ...
Страница 12: ...suring modules U PH PH measuring module 1 Module name Voltage channel 1 Voltage channel 2 Voltage channel 3 Additional measuring modules Apparentcurrentmeas module1 Module name Apparent current channel 1 Apparent current channel 2 Apparent current channel 3 Additional measuring modules Total power Module name Apparent power Active power Reactive power Additional measuring modules Apparent power me...
Страница 13: ... channel 2 Cosine Phi channel 3 Additional measuring modules Frequency Module name Network frequency Additional measuring modules Energy meter Continuous counter active energy Continuous counter reactive energy Additional measuring modules Extras Settings Display firmware version Commissioning Configuration Commissioning Password Module name Scan remove module Reset display Single phase 3 phase me...
Страница 14: ...heck whether the local power supply conditions comply with the specifications on the nameplate A faulty connection may destroy the system The device must be connected in accordance with the connection chart For energy and synchronous pulse input polarity must be observed contact your energy supplier In systems susceptible to lightning lightning protection must be provided for the control voltage b...
Страница 15: ... 24 k3 and 25 l3 Measuring inputs for current The measuring inputs for current must be connected via current transformers x 1A AC or x 5A AC When connecting transformers pay attention to the energy flow direction and the correct assignment of measuring voltage inputs to the current transformers Measuring voltage Messspannung 23 l2 Messstrom Measuring current 21 l1 k1 20 k2 22 25 l3 k3 24 L2 N L3 L...
Страница 16: ...1D4 PS 24V power supply unit via the second module bus interface 3 At the multisys 1D4 power supply unit connect the supply voltage refer to nameplate The operation LED on the device is illuminated green 4 At the terminals 10 L1 11 L2 12 L3 and 13 N connect the measuring voltage the operating voltage of the measuring module 5 At the display select the menu Extras Commissioning to scan measuring mo...
Страница 17: ...gnizes the measuring module and adds it to the list of modules connected 11 You can now scan further modules which are automatically added to the module list or by touching the stop button end the scanning process The display can manage a maximum number of ten modules Set up diagram for operation of the multimess 1D4 with multimess 1D4 DS example LCD Measuring module 1 to 10 maximum multisys 1D4 P...
Страница 18: ...5 release Previous menu Display of measuring module version Display configuration Start commissioning Next menu Display of the firmware version and release of the measuring module at the module bus Measuring module designation BS type module bus device 01 00 version 001 release Selection of next measuring module Selection of previous measuring module Next menu ...
Страница 19: ... the menu item scan 5 After selecting this menu item with the cursor buttons the scan mode can be started with the scan button and the scan display begins to flash This way the scan button at the measuring module close to the status LED flashing green is unlocked 6 By pressing the scan sensor button for approx 4 seconds set the measuring module into scan mode the green status LED flashes more quic...
Страница 20: ...e into scan mode the green status LED flashes more quickly The measuring module is detected and included in the bus list You can now read out and process the data 5 System operation In this chapter you will find instructions on how to operate the multimess 1D4 with the multisio 1D4 DS display in daily use Furthermore it contains references to the complete range of functions 5 1 Configuration of sy...
Страница 21: ...damental power factor Voltage phase neutral conductor Network frequency Active power total 3 phase QS Active power reactive power apparent power total 3 phase YES Confirmation to save configuration NO Discard configuration SCAN Scan mode search mode for module search Firmware Operating software of the measuring module or display module 1x3p 3 phase measurement 3x1p single phase measurement Measuri...
Страница 22: ...n of single phase or 3 phase measurements Configuration of current transformer primary secondary Configuration of voltage transformer primary secondary 5 1 3 Para function With the para configuration function you can display the firmware version of the measuring modules connected change the LCD settings and choose between English and German as the display language 5 1 4 Consumption monitoring In t...
Страница 23: ...ower 5th screen Apparent power for phase L1 L2 and L3 individually 6th screen Active power for phase L1 L2 and L3 individually 7th screen Reactive power for phase L1 L2 and L3 individually 8th screen Cosine Phi for phase L1 L2 and L3 individually 9th screen Power frequency 10th screen Continuous energy meter for active energy consumption Continuous energy meter for reactive energy consumption 11th...
Страница 24: ... overview In this chapter you will find a complete overview of all menus and menu items of the multimess Display of momentary measuring voltage for Phase L1 N Phase L2 N Phase L3 N Display of momentary measuring voltage for Phase L1 2 Phase L2 3 Phase L3 1 ...
Страница 25: ...EBDA0193_1112 1_GB 25 Display of momentary apparent current for Phase L1 Phase L2 Phase L3 Display of total values of Apparent power Active power Reactive power Display of momentary apparent power for Phase L1 Phase L2 Phase L3 ...
Страница 26: ...DEBDA0193_1112 1_GB 26 Display of momentary active power for Phase L1 Phase L2 Phase L3 Display of momentary reactive power for Phase L1 Phase L2 Phase L3 Display of momentary values of cosine Phi for Phase L1 Phase L2 Phase L3 ...
Страница 27: ... frequency Display of the continuous energy meter for reactive energy total value In the submenus the values of the individual phases can be seen Display of the continuous energy meter for active energy total value In the submenus the values of the individual phases can be seen ...
Страница 28: ... 1 1 digit Reactive power 1 1 digit Frequency 0 1 Hz 1 digit 7 1 2 Measuring principle Reading 128 measured values per period A D converter 12 bit Measurement of U and I simultaneous recording of measured values for U and I Update speed complete measuring cycle 1 sec Harmonics calculation DFT with 128 points over one period Frequency measurement Mode Voltage measured between phase L1 L2 L3 N 7 Tec...
Страница 29: ...A provided by the measuring voltage Module bus power supply ext 24VDC 0 3W via RJ12 module bus connector 7 1 5 Hardware inputs and outputs 7 1 5 1 Inputs Measuring inputs for voltage UL1 N UL2 N UL3 N 3 x 50V 230V 280V AC Input impedance 900 kOhm each Ph N Measuring inputs for current IL1 IL2 IL3 3 x 0 02A 5A 6A AC Power consumption _ 0 3 VA per input at 6A 7 1 5 2 Outputs Serial interface Module ...
Страница 30: ...cuit current transformer terminals k and l prior to opening the circuit Input control voltage via measuring voltage Module bus connection Connection material ready made KBR system cable 6 pole modular cable unshielded max length 30m if placed accordingly 7 1 7 Mechanical data Busbar devices Housing measurements 90 x 71 x 61 mm H x W x D Mounting type Wall mounting on DIN rail 7 5mm deep in accorda...
Страница 31: ...g temperature 5 C 55 C Humidity 5 95 non condensing Storage temperature 25 C 70 C Electrical safety Standards and amendments DIN EN 61010 2001 B1 2002 B2 2004 Protection class II Overvoltage category CAT III UPH PH up to 400V Degree of protection IP 20 DIN EN 60529 1991 A1 2000 Electromagnetic compatibility DIN EN 61000 6 1 2007 DIN EN 61000 6 2 2005 DIN EN 61000 6 3 2007 DIN EN 61000 6 4 2007 ...
Страница 32: ...e Module bus RS485 via RJ12 interface Baud rate 38400 7 2 3 Electrical connection Module bus connection Connection material ready made KBR system cable 6 pole modular cable unshielded max length 30m if placed accordingly 7 2 4 Mechanical data Flush mounted device Housing dimensions 96 x 96 x 46 mm H x W x D Mounting cutout 92 x 92 mm according to manufacturer s specifications Protection type Front...
Страница 33: ...tandards and subsequent amendments DIN EN 61010 1 A2 1996 05 IEC1010 1 A2 Protection type IP20 in accordance with DIN EN 40050 part 9 1993 05 Electromagnetic compatibility DIN EN 61000 6 3 2005 06 IEC 61000 6 3 DIN EN 61000 6 2 2000 03 IEC 61000 6 2 7 3 Protective measures 7 3 0 1 Overvoltage and lightning protection It is recommended to install overvoltage protection measures to protect our high ...
Страница 34: ...ns multimess 1D4 BS with multimess 1F96 DS 9 multimess 1D4 BS with multisio 6D6 and multisio 6F96 DS 10 multimess 1D4 BS with multisys 3D2 ESBS 10 Disclaimer 6 Disposal 8 E Explanation of safety relevant symbols 6 F Function Commi 22 Para 22 I Intended use 5 M Measuring inputs for current 15 Measuring voltage 15 Menu overview 24 P Programming 20 Product liability 8 Protective measures 33 S Safety ...
Страница 35: ......
Страница 36: ...EDEBDA0193_1112 1_EN Am Kiefernschlag 7 D 91126 Schwabach Germany Phone 49 9122 6373 0 Fax 49 9122 6373 83 E mail info kbr de www kbr de KBR Kompensationsanlagenbau GmbH ...