KBR multilog 3 Скачать руководство пользователя страница 1

 

 

 

 

 

 

 

 

 

Operating Manual 

Network Analyzer 

multilog 3 

 
 
 
 
 
 
 
 
 
 
 
 

 

multilog 3

Содержание multilog 3

Страница 1: ...Operating Manual Network Analyzer multilog 3 multilog 3...

Страница 2: ...o the most recent version of the operating manual available on our website www kbr de KBR GmbH Am Kiefernschlag 7 D 91126 Schwabach Tel 09122 6373 0 Fax 09122 6373 83 E Mail info kbr de Internet www k...

Страница 3: ...1 Rogowski current clamps 13 4 1 2 Current clamps 14 4 1 3 Accessories for current measurement 16 5 Intended use 17 6 Description 17 7 Hardware multilog 3 18 7 1 multilog 3 Hardware 18 7 2 Accumulato...

Страница 4: ...We take care of it 4 9 multilog 3 App 28 9 1 Connection to multilog 28 10 Maintenance Cleaning 29 11 Calibration 29 12 Disposal 29 13 Product Warranty 30...

Страница 5: ...s to avoid the danger Types of warnings Warnings are distinguished by the type of danger they are warning against DANGER Warns of imminent danger that can result in death or serious injuries if not av...

Страница 6: ...level 1 1 List level 2 2 List level 2 1 5 Applicable documentation For the safe and correct use of the product observe the additional documentation that is delivered with the system as well as the rel...

Страница 7: ...he device only with recommended accessories Ensure that the device is not operated outside the design limits See the technical data Ensure that the original accessories are not operated outside the de...

Страница 8: ...manual Voltage ground USB interface CE marking guarantees compliance with the European directives and regulations regarding EMC The unit is fully protected by double or reinforced insulation IP65 6X...

Страница 9: ...ilog 3 basic The device is suitable for performance analyses for energy audits according to ISO 50001 as a data logger for troubleshooting and for online measurements 1 multilog 3 light This version i...

Страница 10: ...eme values 200ms x Phase angle of current and voltage harmonics x Real apparent and reactive power of harmonics x THD voltage current PWHD PHC x x x Inter harmonics voltage current DC to 10 kHz Ripple...

Страница 11: ...on class CAT IV 600 V Insulation test Impulse voltage 12 8 kV 5 sec 7 4 kV rms A D converter 16 Bit Climate temperature proof Function 20 45 C Storage 30 80 C Power supply AC 100 V 440 V OVC IV 50 60H...

Страница 12: ...of display over Um 1 16 of Udin 0 05 of Udin over Um 1 of Udin Frequency 5mHz over fnom 15 fnom 50 Hz 60 Hz Flicker Pst Plt 5 of display over 0 02 20 of U U Dip residual voltage 0 2 of Udin over 10 10...

Страница 13: ...o 20 kHz 10 Hz to 20 kHz Isolation voltage type 600 V AC DC CAT IV 600 V AC DC CAT IV Accuracy 20 50 Hz 50 A 0 1 of the full scale value 50 3000 A 1 5 of the measured value 100 A 0 1 of the full scale...

Страница 14: ...AC RMS 200 A AC RMS Measurement range 100 mA to 20 A RMS 1 A to 200 A RMS Output voltage 10 mV A 1 mV A Frequency range 40 Hz to 20 kHz 40 Hz to 20 kHz Isolation voltage type 600 V AC 600 V AC Accurac...

Страница 15: ...ges AC DCup to 60 600 A Measurement range AC DC 60 A AC DC 600 A Current range 60 A DC 40A AC RMS 600 A DC 400A AC RMS Measurement range 200 mA to 60 A RMS 600 A RMS Output voltage 10 mV A 1 mV A Freq...

Страница 16: ...output Avoid input voltages at the current inputs greater than 30 V Example Power conversion factor Current conversion correction factor the default is 1 A 10 mV If you use a current clamp with a 500...

Страница 17: ...d data 6 Description The Network Analyzer multilog 3 is suitable for analysis in low medium and high voltage networks It meets all the requirements of the measurement equipment standard IEC61000 4 30...

Страница 18: ...Hardware WLAN Wifi Interface 1 5 voltage leads fix connected L1 red L1 L2 red L2 L3 red L3 N blue N Earth green E USB interface Measurement Start Stopp 2 input for 4 current clamps 1 4 voltage leads...

Страница 19: ...d with energy directly at the measuring point via this adapter and does not require a separate socket The following voltage ranges for the mains supply are possible 88 V 500 V AC or 100V 300V DC High...

Страница 20: ...achieve a long battery life time At 80 capacity the PQ Box can run approximately 2 hours without mains supply The Li ion battery is first charged to 100 when the threshold 75 is reached This has a ver...

Страница 21: ...age network Connection in a 3 phase 4 wire AC network Voltage connection Ensure that voltage measurement cable PE is connected for every measurement If no PE connection is available connect E and N to...

Страница 22: ...connection Ensure that voltage measurement cable E is connected for every measurement If no PE connection is available connect E and N together Ensure that switching 1 wire system is selected Setting...

Страница 23: ...software The input impedance of a measuring input is 1 2 mega ohms If the high resistance ground connection is not desired it is also possible to interconnect the terminals E and N and to hang open N...

Страница 24: ...le connect E and N together Ensure that switching 3 wire is selected Setting via display or software Set the voltage transformer ratio Enter the nominal conductor conductor voltage Set the current tra...

Страница 25: ...evaluation software or device set up Isolated networks Connections Connect voltage measurement conductors E and N to ground If this is not desired in the plant due to isolation monitoring the E and N...

Страница 26: ...device memory Using a key combination at the start of the device it is possible to completely erase the device memory 0 Establish power supply to the multilog 3 0 Orange LED lights up 0 Now press the...

Страница 27: ...x50AP_1804 204 For connection you have to enter the WPA2 Key on your PC or mobile phone SSID and password for a WPA2 connection can be found on the nameplate of the network analyzer Example for SSID P...

Страница 28: ...g via a smartphone A detailed parameterization of the multilog 3 trigger limits ripple control signal analysis is only possible via the WinPQ mobil software 9 1 Connection to multilog 3 The multilog...

Страница 29: ...for voltage leads 500 mA FF 50 kA AC DC 600 V 6 3 mm x 32 mm DANGER Danger to life due to electric shock Do not open the unit Maintenance of the equipment can only be carried out by KBR GmbH For servi...

Страница 30: ...d work manship for a period of three years from the date of purchase 0 For accessories like current clamps and the battery the period is one year 0 This warranty does not cover damage caused by accide...

Страница 31: ...31...

Страница 32: ...We take care of it 32 KBR GmbH Am Kiefernschlag 7 D 91126 Schwabach Tel 09122 6373 0 Fax 09122 6373 83 E Mail info kbr de Internet www kbr de 28230_EDEBDA0324 3123 1_EN_multilog 3_Hardware...