18
COLD DRAFT PREVENTION
In heating mode the fan does not run when the indoor heat exchanger
temperature is equal to or lower than: 0: 15°C (for fresh air indoor unit: 14°C)
1: 20°C (for fresh air indoor unit: 12°C) 2: 24°C (for fresh air indoor unit: 16°C) 3:
26°C (for fresh air indoor unit: 18°C)
FF(default): according to the IDU settings
SHUTDOWN OPERATION
LENGTH
In heating mode when the set temperature has been reached, the fan operates
in “T” minutes off / 1 minute on repeating cycle
T=0 / 1 / 2 / 3 / FF(default)
0: 4 minutes
1: 8 minutes
2: 12 minutes
3: 16 minutes
FF(default): according to the IDU settings
STATIC PRESSURE
High static pressure, fresh air processing unit: 0~19, FF (default)
Others: 0~9, FF (default)
AUTO MODE CHANGEOVER
DELAY
Minimum switching time between auto cooling and auto heating operations
0(default): 15 minutes
1: 30 minutes
2: 60 minutes
3: 90 minutes
KEYPRESS TONE
ENABLED (default)/ DISABLED