8.3 Main Protection
8.3.1 Three minutes delay at restart for compressor.
8.3.2 Sensor protection at open circuit and breaking disconnection.
8.3.3 Indoor fan delayed open function
----When system starts up, the louver will be active immediately, and the indoor fan will open after certain
time.
----If the system runs in heating mode, the anti-cold wind function has priority.
8.3.4 Fan speed is out of control (For the units used DC fan motor)
For console:
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display
the failure.
For other models:
When indoor fan speed keeps too low (lower than 300 RPM) for 50s, the indoor fan will shut off and restart
30s later, if protection happened 3 times when fan motor restart continuously, the unit will stop and the LED
will display the failure.
8.3.5 Inverter module protection
The Inverter module has a protection function about current, voltage and temperature. If these protections
happen, the corresponding code will display on indoor unit and the unit will stop working.
8.4Operation Modes and Functions
8.4.1 Fan-only mode
(1) Outdoor fan and compressor stop.
(2) For Console: Indoor fan can be set to high/med/low/breeze, for other models: Indoor fan can be set to
high/med/low/auto.
(3) The louver operates same as in cooling mode.
(4) Auto fan in fan-only mode acts as follow:
a
b
c
d
T1-24
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
8.4.2 Cooling mode
8.4.2.1 Outdoor fan running rules
T4
A+
A
B
C
D
E
F
G
H
I
While A, B, C
…means different fan speed of outdoor unit.
Содержание Frigicoll KAM-DN7
Страница 1: ...KAM DN7 ...
Страница 2: ...2 ...
Страница 60: ...60 For KAY 26 DN7 For KAY 35 DN7 ...
Страница 61: ...61 For KAY 52 DN7 For KAY 71 DN7 ...
Страница 62: ...62 4 Wiring Diagram KAY 26 DN7 KAY 35 DN7 KAY 52 DN7 KAY 71 DN7 ...
Страница 79: ...79 For KAY S 26 DN7 For KAY S 35 DN7 For KAY S 52 DN7 ...
Страница 80: ...80 For KAY S 71 DN7 ...
Страница 96: ...96 For KAY D 26 DN7 KAY D 35 DN7 For KAY D 52 DN7 ...
Страница 97: ...97 4 Wiring diagram KAY D 26 DN7 KAY D 35 DN7 KAY D 52 DN7 ...
Страница 119: ...119 3 3 Console 16 Drain pipe 195 Hanging arm 700 600 210 ...
Страница 123: ...123 5 Wiring diagram KCI 26 DMN8 KCI 35 DN10 ...
Страница 124: ...124 KCI 52 DMNU9 ...
Страница 125: ...125 KCIS 71 DMNU9 ...
Страница 126: ...126 KPD 20 DMN7 KPD 26 DMN7 KPD 35 DN10 ...
Страница 127: ...127 KPD 52 DMNU8 KPD 71 DMNU8 ...
Страница 128: ...128 KSD 26 DMN6 ...
Страница 129: ...129 KSD 35 DN9 ...
Страница 130: ...130 KSD 52 DMNU8 ...
Страница 131: ...131 6 Static Pressure Duct KPD 20 DMN7 KPD 26 DMN7 ...
Страница 132: ...132 KPD 35 DN10 KPD 52 DMNU8 ...
Страница 133: ...133 KPD 71 DMNU8 ...
Страница 149: ...149 Wiring diagram KAM2 42 DN7 KAM2 52 DN7 ...
Страница 150: ...150 KAM3 62 DN7 KAM3 78 DN7 ...
Страница 151: ...151 KAM4 80 DN7 ...
Страница 152: ...152 KAM4 105 DN7 ...
Страница 153: ...153 KAM5 120 DN7 ...
Страница 196: ......