48
KATANA S610M Inverter Specialized for Elevator Manual
6.7
Control Performance Parameters (Group F06)
Function
Code
Parameter Name
Setting Range
Factory Default
Value
F06.00
zero-speed starting P
1
~
2000
200
F06.01
zero-speed starting I
0
~
9999
100
F06.02
ASR1-P
1
~
200.0
20.0
F06.03
ASR1-I
0
~
9.999
0.200
F06.04
ASR1 output filter
0
~
8 (corresponding to 0
~
2^8/10ms)
0
F06.05
ASR2-P
1
~
200.0
20.0
F06.06
ASR2-I
0
~
9.999
0.200
F06.07
ASR2 output filter
0
~
8 (corresponding to 0
~
2^8/10ms)
0
F06.08
ASR1/2 switching frequency
0.0
~
100.0
%(
F00.07
)
10.0
%
Parameters F06.01
~
F06.08 are effective under vector control. And F06.00 & F06.01 only work within
the maintaining time of zero speed starting (F02.02) under closed loop vector control.
Under vector control, speed response features of vector control can be changed by setting proportional
gain P and integral constant I of the speed regulator.
1
、
The composition of speed regulator (ASR) is as shown in Figure 2-10. K
P
stands for the proportional
gain P, T
I
stands for the integration constant I.
Fig. 6-10 Sketch of speed regulator
When integral constant is set to 0 (i.e. F06.01=0, F06.03=0, F06.06=0), there is no integral action, and
speed loop is a simple proportional regulator.
2
、
Adjustment of proportional gain P and integral constant I of speed regulator (ASR):