33
/
58
specifically designed for Helo's
and Hastor’s wood heated products.) Minimum diameter for the pipe:
125mm. Minimum length: 3.5m.
The remaining flue opening in the back wall must be covered with the plug and screwable plate that
are in the combustion chamber on delivery.
When the connection is made in the back, the modular chimney's attachment goes directly into the
back wall opening (Pictures 2 and 3). For other flue pipes Helo offers specially made adaptors.
ATTENTION! The attachment pipe, the plug and cover plate for the back wall flue opening are
delivered loose in the combustion chamber. When the top opening is used, the back wall plug must
always be pressed tightly into place and the cover plate installed.
When the back wall opening is used, the plug is pressed into the top opening and the cover plate
stored elsewhere.
2.3.1. Masonry flue
The fireplace must be connected to the flue channel with the accompanying connection pipe. Pierce
the chimney’s masonry with a through hole that is 20 mm wider than the outer diameter of the
connection pipe. The aperture between pipe and masonry must be sealed with heat resistant mineral
wool
– do not use plaster! (This ensures the necessary room for movement due to the heat expansion
of the pipe during use). Similarly, the connection pipe may also be attached to the top of the fireplace
by using a 45 degree bent pipe. (Adhere to the required safety distances. For non insulated pipe it is
390 mm to the nearest combustible material.)
2.4. Foundation
Make sure that the supporting floor can carry the weight of the fireplace. The base must also be
smooth and horizontal.
Model
Weight kg
Melody 920 Steel with metal
sides
86
Melody 920 with stone
cladding
287 (307)
Melody 1150 with stone
cladding
344 (366)
MELODY SWING Fireplace
204 (226)
(Weight with the rear wall clad in stone)
If the fireplace is not attached from the back wall to a masonry flue, but from the top, the weight of the
chimney must be accounted for as well. Further information and guidance about the installation can be
requested from the local fire department.
2.5. Safety distances
The given safety distances must be adhered to under all circumstances to prevent fire hazards!
The safety distances are minimum lengths to flammable material.
If the fireplace is installed on a floor that consists of flammable material, a protective plate made of
metal or equivalent fireproof material must be placed in front of it. The plate must extend 400mm in
front and at least 100mm to each side of the feed door.
Safety distances to flammable material
Rear (mm)
Sides (mm)
Above (mm)
Front (mm)
MELODY Fireplace
300
400
600
1000
If the fireplace is connected to a masonry flue that is wider than the fireplace, a 50 mm aperture must
be left in the rear.
Содержание Melody 920
Страница 21: ...21 58...
Страница 46: ...46 58 MELODY MELODY Helo 80 Ceram 800 Coanda www helo fi...
Страница 47: ...47 58 1 1 1 o o o 1 2 2 1 1 3 304 C 600 C 12 6 4 Helo...
Страница 48: ...48 58 2 5 2 4 2 5 2 2 1 2 3 1 2 2 2 2 1 10 11 4...
Страница 51: ...51 58 15 20 2 6 3 2 1 12 5 2 5 25 1 8 7 3 2 2 8 9 8 8 9 8 8 9...
Страница 52: ...52 58 3 2 3 25 33 7 9 1 8 3 7 3 2 4 2 3 3 3 3 3 1 KASTOR NOKI POIS 3 3 2 4 5 3 3 3 3 3 4...
Страница 53: ...53 58 2 4 5 3 5 120 180 15 20...
Страница 54: ...54 58 Helo 6 Helo Helo 3 3 HELO OY Tehtaankatu 5 7 11710 Riihim ki 019 764 360 e mail info helo fi www helo fi...
Страница 58: ...58 58...