1967-A2

Part Number: 11967*

INSTALLATION INSTRUCTIONS

OEM INSTALLATION

• Requires 2 standard 2-1/8” deep junction boxes. One 

for battery and one for Temperature Display unit. Separate 
conduit required for “LINE” and low voltage wiring

• Tape all exposed openings in device boxes before  

foaming panel

• Run wiring for probe from device box to refrigerated  

space. Seal around wires to prevent moisture from entering 
device box 

• Run battery cable to battery junction box. This allows 

battery to be replaced

• Run power wiring 14 AWG min., crimp and secure  

1/4 spade insulated female connectors to all wires. Follow all 
manufacturing recommendations for installation of connectors

• All wiring must comply with local code
• Test display by temporarily applying a 9 volt battery  

to the battery connector

• Display will cycle through a test program and show 

temperature. Display will flash temperature. Remove battery 
for shipping 

FIELD WIRING

• Once the unit has been wired using supplied wiring schematic, 

connect the 9 volt battery. Connect power to circuit 

BATTERY

• Never place 9 V battery in freezer 
• Never use lithium ion batteries 

OPERATION

• Light Control: Press rocker switch to turn lights ON
• Unit Change: To change temperature units from °F to °C, 

install the small black jumper on the back of unit. This is 
found in the bag with mounting screws

• Battery Voltage Monitoring: The far right decimal point will 

flash if the battery voltage gets too low to operate the unit 
properly. In battery-only mode, the display will turn on and 
off to conserve battery life

Caution: Risk of Electrical Shock 

Turn off breaker at all energized switches before making 
any electrical connections.

Warning

 

This item may contain chemicals known to cause cancer 
or reproductive harm in the state of California. 
www.p65warnings.ca.gov

ERRORS AND TROUBLESHOOTING

• Display reads “HOT”, “OFF”or “- - -”: Connect temperature 

probe or replace probe. 

• Temperature doesn’t change fast enough: The temperature 

sensor is encapsulated in epoxy and wrapped in a tube. 
This encapsulation is designed to simulate product mass 
and not be effected by door opening or defrost cycling.

• Low Battery or “LoBat” is blinking: The battery is not 

installed or the battery charge is too low to allow unit to 
operate. Replace battery 

• Power goes off and display goes blank: The battery is not 

installed or the battery charge is too low to allow unit to 
operate. Replace battery

DESIGN CRITERIA

• Electrical Rating

 

– Voltage: 120 VAC (240 VAC special order) 

 

– Load: 20 AMP resistive/general use 

 

– Temperature sensing and display range  

-40°F [-40°C] to 104°F [40°C]

 

– Resolution: 1° +/- .5°C

 

– Mounting: Inside cooler, outside cooler,  

and outside freezer 32°F [0°C] to 72°F [22°C]

Part No.

Description

119670000A2

Temp Display w/ Kason (120 VAC)

119670000A2240

Temp Display w/ Switch (240 VAC)

91967000942

Temperature Probe, 72 in [6 ft]

919670094224000

Temperature Probe, 240 in [20 ft]