17
/
Troubleshooting
Problem
Solution
Unit won’t
start up
1.
Check if the LED is illuminated.
2.
Check the circuit breaker in your electrical
panel.
3.
Check the unit’s circuit fuse/breaker.
4.
Check the 24-volt circuit, as follows:
Try to establish electrical contact in a wall inlet
between the two metal contacts with a metal
object (e.g. a coin).
•
If the unit starts, the suction hose is
defective.
•
If the unit doesn’t start, check to see if the
24-volt wires are properly connected to
the unit. Try to establish an electrical
contact between the two terminals of the
24-volt circuit on the unit with a metal
object (e.g. a screwdriver).
•
If the unit starts, a 24-volt wire is either cut
or disconnected from one of the wall
inlets.
•
If the unit won’t start up after these steps,
the printed circuit is defective.
Unit won’t
shut
down
Check the 24-volt circuit as follows:
Disconnect one of the two wires on the unit’s 24
-
volt circuit.
•
If the unit shuts down, the problem could
be that two 24-volt wires are touching
each other somewhere or that the wall
inlet is defective.
•
If the unit doesn’t shut down, the printed
circuit is defective. Unplug the power cord.